Table C-19
Simulation
Modbus ad‐
dress
Data type /
Size [bytes]
Parameter
Description
Default value
[unit]
Value
range
Access
level
2764
Float / 4
Mass flow Simulation
Value
Set mass flow simulation val‐
ue.
The mass flow will be set to
this value on all outputs,
if Simulation Mass Flow is
enabled
0 [kg/s]
-1023 to
+1023
Read /
Write
2766
Float / 4
Density Simulation
Value
Set density simulation value.
The density will be set to this
value on all outputs, if Simu‐
lation Density is enabled
1000 [kg/m
3
]
-20000 to
+20000
Read /
Write
2768
Float / 4
Media Temperature
Simulation Value
Set media temperature simu‐
lation value. The media tem‐
perature will be set to this
value on all outputs if Simu‐
lation media Temperature
is enabled
0 [°C]
-50 to +200 Read /
Write
2770
Float / 4
Frame Temperature
Simulation Value
Set frame temperature simu‐
lation value.
The frame temperature will
be set to this value on all out‐
puts if Simulation Frame
Temperature is enabled
0 [°C]
-50 to +200 Read /
Write
2772
Float / 4
Volume flow Simula‐
tion Value
Set volume flow simulation
value.
The volume flow will be set
to this value on all outputs,
if Simulation Volume Flow
is enabled
m
3
/s
-65 to +65
Read /
Write
2780
Unsigned / 2 Enable Simulation
Activate simulation.
Select one of the following
values:
• Bit 0: Mass flow
• Bit 1: Density
• Bit 2: Volume flow
• Bit 3: Media temperature
• Bit 4: Frame temperature
0
0 to 63
Read /
Write
Modbus communication FCT010
C.4 Modbus holding registers tables
SITRANS MASS 2100 & FC300 (FCT010/DSL)
Operating Instructions, 06/2020, A5E39788682-AB
173