Table C-13
Zero point adjustment
Modbus ad‐
dress
Data type /
Size [bytes]
Parameter
Description
Default value
[unit]
Value
range
Access
level
2132
Unsigned / 2 Zero Point Adjust‐
ment
Select zero-point adjustment
method. Automatic zero
point adjustment is recom‐
mended.
• 0 = Auto
• 1 = Manual
0
0 to 1
Read /
Write
2133
Float / 4
Manual Zero Point
Offset
Enter agreed zero point off‐
set value for manual zero
point adjustment mode.
0 [kg/s]
0 to 1023
Read /
Write
2135
Unsigned / 2 Zero Point Duration
Define duration of zero point
adjustment.
30 [s]
1 to 999
Read /
Write
2136
Float / 4
Standard Deviation
Standard deviation during
auto zero point adjustment
0 [kg/s]
-1023 to
+1023
Read only
2138
Float / 4
Standard Deviation
Limit
Set limit for zero point adjust‐
ment Standard Deviation
value. If the Standard Devi‐
ation exceeds the Standard
Deviation Limit, the auto
zero point adjustment is
aborted.
Sensor size
specific [kg/
s]
1)
0 to +1023
Read /
Write
2140
Float / 4
Zero Point Offsett Lim‐
it
Set limit for zero point offset.
If the zero point offset ex‐
ceeds the zero point offset
limit, the zero point offset
cannot be stored
Sensor size
specific [kg/
s]
1)
-1023 to
+1023
Read /
Write
2142
Float / 4
Zero Point Offset Val‐
ue
Default zero point offset
based on factory calibration
of sensor.
A Zero point offset compen‐
sates for sensor variations
due to process conditions.
0 [kg/s]
-1023 to
+1023
Read only
2144
Unsigned / 2 Zero Point Adjust Pro‐
gress
Shows the progress of the
currently running Zero Point
adjustment in percentage
0 [%]
0 to 100
Read Only
Modbus communication FCT010
C.4 Modbus holding registers tables
SITRANS MASS 2100 & FC300 (FCT010/DSL)
Operating Instructions, 06/2020, A5E39788682-AB