LED module and LED module (red/yellow, yellow) 

Description 

 

13 

Siemens Industry, Inc. 

 

A6V10315030_b_en_-- 

Building Technologies Division 

 

2013-06-04 

 

2

 

LED module and  

LED module (red/yellow, yellow) 

 

2.1

 

Description 

The LED module and the LED module (red/yellow, yellow) are zone indicators which 

allow events (e.g. alarms and troubles) from 24 zones to be displayed.  
The LED module has a bicolored LED (red/green) and a yellow LED per zone. It is 

installed in the FCM2019 operating unit (+LED) and in the FCM2023 option module 

(LED). 
The LED module (red/yellow, yellow) has a bicolored LED (red/yellow) and a yellow 

LED per zone. It is installed in the FCM2035 operating unit (+LED) and in the 

FCM2034 option module (LED red/yellow, yellow). 
Features: 

  LED indicator for 24 zones max. 
  Configurable selection of events per zone that are displayed 
  Configuration of LEDs with the Engineering tool set. 
  A maximum of four LED modules can be installed in a window 

firealarmresources.com

Summary of Contents for FCM2018-U3 Series

Page 1: ...A6V10315030_b_en_ Siemens Industry Inc 2013 06 04 Building Technologies Division FCM20xx U2 FCM20xx U3 Operating unit Operating unit LED Mounting Installation firealarmresources com ...

Page 2: ...ent as well as utilization of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www ...

Page 3: ...1 1 Description 4 1 2 Mounting and wiring the operating unit 6 1 3 View of PMI mainboard 9 1 4 Indicators 10 1 5 Adjustment elements 11 1 6 Technical data 12 2 LED module and LED module red yellow yellow 13 2 1 Description 13 2 2 Views 14 2 3 Adjustment elements 15 2 4 Technical data 16 3 FCC Statement 17 firealarmresources com ...

Page 4: ...ng unit LED 1 1 Description The operating unit is installed in the panels and comes in three versions FCM2018 operating unit with control and display elements FCM2019 operating unit LED with extra integrated LED module FCM2035 operating unit LED with extra integrated LED module Each operating unit has an integrated PMI mainboard FCM2027 with the CPU module MPC8248 and the expansion slots firealarm...

Page 5: ...splay 8 lines Buzzer Configurable LED indicators Operating buttons Inscription strips for sliding in Operation can be released with a password or key switch optional Additional functions of FCM2019 operating unit LED 24 zone indicator with LEDs A bicolored LED per zone red green A yellow LED per zone Indication of any events Additional functions of FCM2035 operating unit LED 24 zone indicator with...

Page 6: ...cal The operating unit can also be installed on the outer door in place of the clear glass window Installing the operating unit 4 3 1 2 Installing the operating unit on the inner door rear view 1 Inner door with window FHD2004 2 Operating unit FCM20xx 3 4x fixing nut for operating unit 4 4x set screw for operating unit welded Installation steps 1 Plug the operating unit 2 onto the set screws 4 of ...

Page 7: ...ings of operating unit 2 Wiring to modules of operating unit 3 DIN rail kit FHA2031 4 Periphery bus connection on periphery board X201 5 Ribbon cable fixing with cable support 6 Peripheral data bus connection on PMI mainboard X3 7 Inner door with FCM2018 operating unit 8 Peripheral data bus connection output X402 to further LED modules or option module 9 Peripheral data bus connection input for LE...

Page 8: ...l kit 3 as shown and fix these cables with cable ties 4 Insert the supplied inscription strips underneath the operating unit film as shown in the figure below 5 Swivel the inner door towards the panel and secure it using the locking screw Inserting the inscription strips 1 2 3 5 4 Inserting the inscription strips into the operating unit 1 Inscription LEDs 2 Inscription for the standard keys in the...

Page 9: ...ing unit FCM20xx 1 View of PMI mainboard 9 Siemens Industry Inc A6V10315030_b_en_ Building Technologies Division 2013 06 04 1 3 View of PMI mainboard Equipment for PMI mainboard FCM2027 firealarmresources com ...

Page 10: ... Buzzer Switch keys S32 Reset key S33 Switch for ground fault supervision of the Ethernet connection S37 Support for license key S38 Switch for ground fault supervision of the system supply 1 4 Indicators LED Color Function Condition Meaning H37 Yellow Diagnosis 1 Off Normal operation On Ground fault present H38 Yellow Diagnosis 2 Not used H39 Yellow Diagnosis 3 Not used H50 Yellow MSP fail proces...

Page 11: ...h other buttons Operation Function Press for 2 s Panel is shut down and restarted in a controlled manner This procedure takes up to five minutes Press for 2 s Panel is shut down and restarted immediately This may lead to data loss This procedure takes up to two minutes Press S32 Reset or Acknowledge front operating buttons at the same time Restore factory settings or update firmware Restore factor...

Page 12: ...d with S33 Electrically isolated components such as the network module SAFEDLINK or RS485 module have their own supervision and are not included in the deactivation of ground fault supervision S38 Position Function On Ground fault supervision activated Off Ground fault supervision deactivated 1 6 Technical data Supply input Voltage DC 24 V Standby current display illumination off 130 mA Alarm curr...

Page 13: ... a bicolored LED red green and a yellow LED per zone It is installed in the FCM2019 operating unit LED and in the FCM2023 option module LED The LED module red yellow yellow has a bicolored LED red yellow and a yellow LED per zone It is installed in the FCM2035 operating unit LED and in the FCM2034 option module LED red yellow yellow Features LED indicator for 24 zones max Configurable selection of...

Page 14: ...307 H308 H312 H310 H311 H315 H313 H314 H318 H316 H317 H321 H319 H320 H324 H322 H323 H327 H325 H326 H330 H328 H329 H333 H331 H332 H336 H334 H335 1 2 H372 H370 H371 H369 H367 H368 H366 H364 H365 H363 H361 H362 H360 H358 H359 H357 H355 H356 H354 H352 H353 H351 H349 H350 H348 H346 H347 H345 H343 H344 H342 H340 H341 H339 H337 H338 X407 X409 Printed circuit board view of rear of LED module firealarmreso...

Page 15: ...tput X407 Not used X409 Not used 2 3 Adjustment elements Switches 1 4 S15 are used to assign an address to the LED indicator Switches 5 and 6 S15 can each be used to run an LED test Switch S15 Address 1 1 2 3 4 5 6 20 ON 21 ON 22 ON ON 23 ON 24 ON ON 25 ON ON 26 ON ON ON 27 ON 28 ON ON 29 ON ON 30 ON ON ON 31 ON ON 32 ON ON ON 33 ON ON ON 34 ON ON ON ON 35 ON LED test red ON LED test yellow Empty ...

Page 16: ...chnical data Supply input Voltage DC 24 V Operating current Max 5 mA 1 mA per LED max 48 LEDs Supply output Voltage DC 24 V Current Looped max 1 A LEDs Quantity 48 LEDs for 24 zones LED module 24 LEDs bi color red green 24 LEDs yellow LED module red yellow yellow 24 LEDs bicolored red yellow 24 LEDs yellow Function Can be configured with Engineering tool set Connections Peripheral data bus input a...

Page 17: ...ate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Operation of t...