Operation
Activation / Deactivation / Reset
5
87 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
5.13.5 Activating evac controls
1. Select 'Main menu' > 'Functions'.
The 'Functions' window is open.
2. Select 'Activate / Deactivate'.
A list of all element categories on which a command of the 'Activate /
Deactivate' command group can be executed is indicated.
3. Select the 'Evac control group' element category.
The 'Enter address' window is open.
4. Press <ok> without entering an address.
A list with all 'Evac controls' is open if more than one Evac category has
been configured.
5. Select an 'Evac control group' and press <softkey 1>.
The 'Select command' window is open.
6. Select 'Activate/EVAC'.
'Evac control' is activated.
The window with the command response is open.
Example for the activation of 'Evac control'
Functions
Exit with <C>
Access level 3
On / Off
Test
Activate / Deactivate
Information
(1)
(2)
(3)
(4)
Configuration
Maintenance
All functions
(5)
(6)
(7)
Function
On/Off
Function
All
LED
test
κ
Select 'Activate / Deactivate' menu item, continue with <ok>
Selecting element category
Area
Zone
Sounder
Evac control group
↑ Fire control group
(1)
(2)
(3)
(4)
(5)
κ
Select 'Evac control group' element category, continue with <ok>
Enter address
Evac gr --------
Confirm with <ok>/Exit with <C>
Delete with <Cursor up>
κ
Continue with <ok> without entering an address