Setup of the Person Machine Interface
Person Machine Interface with FBP [AU]
3
23 | 184
Building Technologies
A6V10211076_i_en_--
Fire Safety
2015-12-15
<Reset>
Resets all events that can be reset (password required).
<Alarm delay off>
● Switches off the alarm delay for all events.
● In the event of an alarm, the remote transmission or ↑ global alarming is
activated immediately.
<Premises manned>
● Switches between 'Manned operation' and 'Unmanned operation' operation
modes (password required).
● Opens the event list in case of a "mixed" condition (↑ visibility on several
'Areas' with different 'Manned operation' and 'Unmanned operation' settings).
<Alarm device>
Deactivates the ↑ alarm devices in the event of alarm (password required).
Configurable buttons
The two buttons a and b in the figure above are configurable standard buttons.
You can, for example, configure these two buttons with the following functions:
● 'Poll RT counter'
● 'Non-MCP zones OFF'
3.1.4 Other alarms
Pressing the 'More alarms' button opens the 'ALARMS' event list.
If the 'ALARMS' event list is already open, <More alarms> assumes the function of
the button <▼>, changing to the next alarm event upon activation.
3.2 Person Machine Interface with FBP [AU]
The operating unit [AU] includes the PMI [AU] with the 'Fire brigade panel' (FBP),
through which the fire detection installation can be operated. All important
information from the fire detection installation is indicated spontaneously on the
PMI or can be polled there.
Fire brigade operation
Fire brigade operation is enabled with the key switch. The fire brigade has access
level 2,1. The <Silence buzzer>, <Silence Alarm>, <Reset>, <Disable>, and
<SEVERAL ALARMS> buttons can be operated by the fire brigade .
Full operation
Full operation of all buttons from access level 2,2 can only be enabled with the
PIN.