background image

A6V10207176_h_en_--
2016-05-23

Building Technologies

Control Products and Systems

FC724

Cerberus

 PRO

Fire control panel

FS720 series, IP6

κ

Compact, pre-assembled, microprocessor-controlled fire control panel with
integrated operating unit for up to 504 addresses

κ

Fire control panel can be used as a standalone version or can be networked

κ

Up to 64 stations – control panels and terminals – can be linked to form a
network

κ

Integrated degraded mode function

κ

Redundant network node, degraded mode operation according to EN 54

κ

Fast Ethernet interface for a heterogeneous network

κ

Integrated user-friendly operating unit

κ

Can be extended by adding printer, key switches, LED indicators

κ

Slots for RS232 and RS485 serial interfaces

κ

Emergency power supply for emergency operating time of up to 72 hours

κ

Detection and automatic reading in (auto-configuration) of all C-NET devices,
ready for operation immediately

κ

Processes signals from Cerberus PRO FD720 detector series

κ

Floor repeater displays, floor repeater operating units, and alarm devices on C-
NET detector line

κ

Flexible configuration of complex applications and controls

κ

Configuration data can be uploaded/downloaded via remote access

κ

Firmware for all processor-controlled control panel components can be
updated

Summary of Contents for FC724

Page 1: ... interface for a heterogeneous network κ Integrated user friendly operating unit κ Can be extended by adding printer key switches LED indicators κ Slots for RS232 and RS485 serial interfaces κ Emergency power supply for emergency operating time of up to 72 hours κ Detection and automatic reading in auto configuration of all C NET devices ready for operation immediately κ Processes signals from Cer...

Page 2: ...24VDC ext 2 in outputs optionally Detection line collective Siemens Synova SynoLINE300 or SynoLINE600 TM FDCIO223 Conventional horn line via FCI2009 A1 Transmission of an alarm signal Transmission of a fault signal Fire control panel Fire controls FC724 Repeater FN2002 Cluster C WEB SAFEDLINK Remote access Engineering Tool Operating Tool FC724 FT724 OP720 Mimic display FT2001 A1 DBS721 DBS729 FT20...

Page 3: ...nals can be linked to form a cluster C WEB SAFEDLINK network If the cluster is connected to a danger management system via BACnet up to 16 control panels and terminals can be networked Siemens Danger Management System DL3750 Matrix printer RS232 FC722 FT724 FC72x Cluster C WEB SAFEDLINK 16 stations In Outputs Ethernet FC724 Repeater FN2002 ...

Page 4: ...n_ 2016 05 23 An optical Ethernet network C WEB LAN allows up to 14 clusters with up to 16 stations to be operated on one network A maximum of 64 stations is supported in total You will find details of system networking in product data sheet A6V10227649 ...

Page 5: ...ing unit CPU module and electronics Ethernet connection Slots for RS232 and RS485 modules and network modules SAFEDLINK Space for Kaba or Nordic key switch Space for event printer Peripheral data bus connection for optional LED modules Periphery board The following elements are available on the periphery board Connection terminals for C NET lines remote transmission alarm fault horn output configu...

Page 6: ...ustrial plants regional banks or office complexes Thanks to the flexible networking options the FC724 can also be used for large scale sites Operation Each control unit has an integrated operating unit The control panel can also be operated via a separate FT724 fire terminal You will find details and more information in product data sheet A6V10207898 ...

Page 7: ...398 x 183 mm 430 x 796 x 183 mm RS232 interface Empty housing for free use For installation in all control panels RS232 module must RS232 module must be ordered separately be ordered separately Operating accessories E g for extra batteries FCM7213 Y3 FCM7214 Y3 Operating add on or 48 indicator groups with 96 indicator groups with Event printer one red green one yellow LED each one red green one ye...

Page 8: ...Basic equipment Designation Comment 1 Housing Comfort FH7203 Z3 Items 1 6 Basic equipment 2 Periphery board 2 loop FCI2002 A1 3 Power supply SV 24V 150 W V24230 Z6 A5 4 Mains terminals on TS35 DIN rail Space for socket relay modules 5 Operating unit FCM72xx xx Operating unit with CPU 6 Card cage 2 slots FCA2008 A1 For two module bus cards 7 Space for batteries 2x 12 V 17 26 Ah ...

Page 9: ... peripheral devices with RS485 interface 15 RS232 module isolated FCA2001 A1 For devices with an RS232 interface 16 Network module SAFEDLINK FN2001 A1 For networking several stations 17 Repeater SAFEDLINK FN2002 A1 For extending the C WEB system bus max 1x repeater SAFEDLINK between two stations mounted directly on a plane surface on a TS35 U rail or in housing FDCH221 18 Sounder module FCA2005 A1...

Page 10: ...t Monitored outputs Alarm Fault Horn Freely programmable inputs outputs 1 1 1 1 2 12 Operating unit Integrated Slots for RS232 RS485 serial ports 2 Slots for network modules 2 Slots for loop extension 2 Mounting spaces for cable kit communication 2 Sounder module Max 2 Ethernet port RJ45 1 Operating temperature 8 42 C Storage temperature 20 60 C Air humidity no condensation permitted 95 rel Dimens...

Page 11: ...add on 2xLED indicator 2 600 kg FCM7214 Y3 S54400 B150 A1 Operating add on 4xLED indicator 2 800 kg FHA2016 A1 A5Q00020179 19 mounting kit 3 000 kg FN2006 A1 S54400 A109 A1 Fiber network module SM 0 770 kg FN2007 A1 S54400 A110 A2 Fiber network module MM 0 770 kg Auxiliary power supply FP2003 A1 A5Q00016005 Power supply kit 70 W 0 650 kg FP2004 A1 A5Q00020825 Power supply kit 150 W A for installat...

Page 12: ...nal Headquarters Gubelstrasse 22 CH 6301 Zug Tel 41 41 724 24 24 www siemens com buildingtechnologies Siemens Switzerland Ltd 2008 Technical specifications and availability subject to change without notice Document no A6V10207176_h_en_ FS720 manual Edition 2016 05 23 ...