Operation
Operations under access level 2
8
A6V10421795_en--_k
79 | 151
8.5.2.2 Lamp test
The lamp test checks the following functions:
● LEDs
● Buzzer
● LCD
This function is available directly under Main menu for access level 1 if checkbox
'Lamp test activation possible at access level 1' is checked under task card 'Other
settings' in 'FC360 Panel Configurator'.
1. Press
on the keypad. The 'Main menu' window is open.
Main menu L2
1 - System status
2 - Operation
3 - Event memory
4 - Login
5 - Lamp test
7 - Logout
2. Select 'Operation' and press
. The 'Operation' window is open.
Operation L2
1 - Isolation
2 - Test
3. Select 'Test' and press
. The 'Test' window is open.
Test L2
1 - Detection
2 - Lamp test
3 - Voice test
4. Select 'Lamp test ' and press
. A confirmation dialog window is open.
Do you want to activate
lamp test?
Yes (OK) or No (C)
5. Press
to confirm. Test starts:
● LEDs: on 10 s
● Buzzer: on 10 s
● LCD: on 5 s, then off
The panel returns to the previous status after finishing check.