Commissioning
General commissioning steps
10
A6V10421795_en--_k
111 | 151
● Some devices are assigned to corresponding device types automatically (see
Appendix E: Device type list [➙ 138]
● Create default control logics as per pre-definition.
10.4.2 Configuring the system manually
NOTICE
Before configuring the system manually, make sure that the panel is in normal
operation.
To modify using 'FC360 Panel Configurator'
1.
Connect PC to the panel. See chapter '
Connecting a PC to the panel [➙ 107]
2.
Open a web browser.
3.
Enter web address with 'fc360.siemens.com' and press <Enter>.
'FC360 Panel Configurator' is open.
4.
Enter access level 3 password to log into access level 3.
5.
Modify configuration as needed.
Generally the following configuration may be modified in 'FC360 Panel
Configurator':
– Customer texts
– Properties and parameter settings
– Allocation of devices and zones
– Control logics
6.
After finishing modification, click 'Apply'.
A confirmation window is open.
7.
Click 'OK' to download the modified configuration to the panel. (The panel is at
access level 3.)
The panel restarts automatically.
The configuration finishes.