Frame these instructions and mount them near the control panel for operator reference.
FSD901 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the
Alarm
LED flashes, LCD displays alarm condition and the buzzer sounds. Local
audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel
are accounted for and notify the Fire Department to advice of the alarm and/or verify that an automatic
signal has been received at the Fire Department.
Authorized Personnel Only
To acknowledge the alarm:
To acknowledge the alarm, enable the control buttons by operating the key switch, and press the
Acknowledge
button. The local buzzer will be silenced, and the
Alarm
LED will change from on-
flashing to on-steady.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted
,
press the
Signal Silence
button. The silenceable notification appliances will be silenced, and LED indications will change
from flashing to continuous. The
Signal Silence
LED will be lit.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Signal silence inhibit (if set) prevents the alarm from being silenced for a
predetermined time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing
the
Reset
button.
Trouble Operation
Trouble is indicated by:
Trouble
LED flashes and LCD displays trouble conditions. Panel buzzer sounds (pulsing).
To acknowledge the trouble:
Enable the control buttons by operating the key switch and press the
Acknowledge button
.
The
Trouble
LED turns on-steady. When the trouble condition has been cleared, you may need to
reset the panel to restore to a normal standby condition.
Warning: Devices in trouble condition may not report a fire alarm.
Event Scrolling
Viewing Events on the System:
Events are displayed in the system by event priority (Unacknowledged Alarm > Unacknowledged
Supervisory > Unacknowledged Trouble > Acknowledged Alarm > Acknowledged Supervisory >
Acknowledged Trouble > Status > Test) followed by event occurrence (latest to oldest event) in a
circular list.
According to settings, some events can be suppressed (not display) on annunciator.
Normal Standby Condition
The green
AC Power On
LED will be lit and no other indicators on.
For service, contact: ___________________________________________
Telephone Number: _____________________________________________
Frame these instructions and mount them near the annunciator for operator reference.
firealarmresources.com
Summary of Contents for FC2005
Page 5: ...firealarmresources com ...
Page 33: ...28 FC2005 Enclosure Mounting Pictures firealarmresources com ...
Page 48: ...43 firealarmresources com ...
Page 58: ...53 This page is left intentionally blank firealarmresources com ...
Page 89: ...84 LE4010 CF Configuration Reference from DSC Installation Manual firealarmresources com ...
Page 90: ...85 TL300 CF Configuration Reference from DSC Installation Manual firealarmresources com ...