Cell Control Board - 10000432
MicroHarmony Cell Sizes 40 - 260A Manual
5-4
19001467: Version 1.0
s
5
5.4.3
OOS Detection/Latch
Out of Saturation is detected by monitoring Vce of the IGBT. Each fault feedback from the gate drive channels goes
through a two-shot circuit that verifies that two consecutive OOS (Out-of SAT) faults occur before the drive trips.
This provides extra immunity from false OOS faults. OOS is annunciated within 10 to 14
μ
S after second OOS
pulse.
5.4.4
Bus Voltage Sensing and Protection
Three differential amplifiers are used to m to - bus, +2/3 to - bus, and +1/3 to - bus. These analog signals are
filtered and scaled 1:-100, named P1DET, P2DET, and P3DET.
1.
Capacitor Voltage Monitoring
P1DET and P2DET are summed and scaled to produce a 1/3 bus voltage signal divided by 100. Likewise,
P2DET and P3DET are summed and scaled, and P3DET and agnd are summed and scaled. Each of these 3
signals are compared to a fixed 10VDC reference to a diode AND circuit. In the event that any 1 signal
exceeds the scaled threshold (430V for 400V caps and 484V for 450V caps), then VCAP_OK annunciates a
“Cap share Fault” and trips the cell. Three select resistors are used for trip point scaling.
2.
Bus Voltage Monitoring
P1DET is filtered and scaled for Vbus/255 and compared to a fixed 10V reference that is scaled for the
appropriate over voltage trip point. In the event that the bus voltage exceeds the scaled threshold, VDC_HIL
annunciates a “DC Bus over voltage Fault” and trips the cell. (630V cell trips at 1084VDC, 690V cell trips
at 1200V, 750V cell trips at 1300V). A solder blob jumper is used for trip point scaling.
The filtered and scaled P1DET (Vbus/255) is also compared to a scaled 10V reference for low bus fault
annunciation. If the DC bus drops below 475VDC, VDC_LOWL will annunciate a “Low Bus Fault” and
trip the cell.
The filtered and scaled P1DET (Vbus/255) is also compared to a scaled 10V reference for voltage available
fault annunciation. If the DC bus drops below 300VDC, POWER_OK will annunciate a “Control Power
Fault” and trip the cell. When the bus is below 300VDC, the CCB SMPS may not operate properly and must
shut down.
Summary of Contents for Eupec
Page 16: ...Cell Overview MicroHarmony Cell Sizes 40 260A Manual 1 6 19001467 Version 1 0 s 1 ...
Page 36: ...Installation MicroHarmony Cell Sizes 40 260A Manual 3 4 19001467 Version 1 0 s 3 ...
Page 42: ...Electrical Description MicroHarmony Cell Sizes 40 260A Manual 4 6 19001467 Version 1 0 s 4 ...
Page 56: ...Repair Hints MicroHarmony Cell Sizes 40 260A Manual 8 4 19001467 Version 1 0 s 8 ...
Page 76: ...Drive Calc Express MicroHarmony Cell Sizes 40 260A Manual 10 2 19001467 Version 1 0 s 10 ...
Page 86: ...Communication Protocol MicroHarmony Cell Sizes 40 260A Manual 11 10 19001467 Version 1 0 s 11 ...
Page 87: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 1 s NOTES ...
Page 88: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 2 19001467 Version 1 0 s ...
Page 89: ...MicroHarmony Cell Sizes 40 260A Manual NOTES 19001467 Version 1 0 N 3 s ...
Page 90: ...NOTES MicroHarmony Cell Sizes 40 260A Manual N 4 19001467 Version 1 0 s ...