RXB application library (KNX)
FNC – Fancoil-Applikationen aus FC-10, FC-11, FC-12 CM110672en_0
3
Building Technologies
FNC05 – Four-pipe fan coil with electric reheater
30.11.2007
FNC05
Four-pipe fan coil with electric reheater
KNX
R
•
Heating with LTHW and cooling with CHW.
•
Modulating control of heating and cooling valve.
•
Heating with electric reheater
•
Automatic or manual fan control.
Plant diagram
N1 Room
controller.
R1
Room unit with temp.
sensor.
B1
Return air sensor.
D1 Window
switch.
D2 Presence
detector.
D3
Safety thermostat electric
reheater.
Q1
Fan (1… 3-speed).
YH Heating
valve.
YC Cooling
valve.
YR Electric
reheater.
1038
5S
13
T
B1
YC
YH
Q1
N1
R1
D1
D2
T
D3
YR
KNX
R