121/166
Siemens
RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12 CM110385en_05
Building Technologies
Master/slave
28 Feb 2009
•
The master/slave function requires that all 3 M/S zones have the same name
•
If the master/slave function is not required, the M/S zone should be disabled (to limit
the load on the bus).
HandyTool
Parameter
Short name
Basic setting
*021
Master/Slave
Master
*022
Master/Slave
zone
(apart.)
1
*023
Master/Slave zone (room)
–1 (out of service)
*024
Master/Slave
zone
(subzone)
1
Parameter Setting
HandyTool
*021
Master/Slave
Master
1
Slave
0
10.2.1 Window switch (LTE mode)
For master/slave mode, only the master's window switch is evaluated without special
measures, which also influences the slave controllers.
Window switches on the slaves are NOT considered.
10.2.2 Presence detector (LTE mode)
For master/slave mode, only the master's presence detector is evaluated without
special measures, which also influences the slave controllers.
Presence detectors on the slaves are NOT considered.
Notes