RXB (KNX) application library
FNC Description of functions for FC-10, FC-11, FC-12
CM110385en_05
Building Technologies
Room operating modes
28 Feb 2009
Effective occupancy (Output communication object)
Flags
R W C T U
Type Send
hearbeat
States
1 0 1 1 0 20.003
DPT_OccMode
Yes
0 = Occupied
1 = Standby
2 = Unoccupied
5.3.4
Central control of room operating mode via
the
Room operating mode
time
schedule
This type of time schedule is not supported in DESIGO. If it is nevertheless used, this
can cause room controller errors.
5.3.5
Local control of room operating mode with a room unit
Room unit
S
Central
Local
1.
2.
3.
S
DI
S
S
S
DI
S
3.
Controller
Prio
PPS2
3.
S
The /Auto button on the room unit can be used like
an occupancy button.
The room user can use it to decrease or increase the
room temperature control.
The room unit is connected to the PPS2 interface on the room controller.
It displays the effective room operating mode in a simplified form, and can also be used
to change it:
State
Description
Auto
Effective room operating mode is
Comfort
Reduced mode
in the room, depending on the Priority 1, 2 and 3
influences:
The
effective room operating mode
is
Precomfort, Economy
or
Protection.
(3rd priority: "last one wins ").
•
The
effective room operating mode
can be changed via the room unit only during the
building-in-use period (defined by the
Use
time schedule)
•
The change in the
effective room operating mode
is event-driven, the key factor
being the moment when the button on the room unit is pressed.
•
The
Effective occupancy
or
Temporary Comfort mode
(both Priority 3) can cause the
effective room operating mode
to change again
Æ
the last command always applies.
Effective