110/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
General / central functions
28 Feb 2009
10.13.2 LTE mode
Enable alarm info can also be operated in LTE mode. Here, two types of information
are provided:
AlarmInfo_CS
and
AlarmText_CS
.
With Synco, the user does not need to deal with this, as connection is opened
automatically.
The device in this case is active on the bus and sends its alarm as soon as it receives
highest alarm priority. This ensures that the control station does not miss alarms.
AlarmInfo_CS (Output)
Possible partner function blocks
Known partner devices
AlarmInfo_CS
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
AlarmText_CS (Output)
Possible partner function blocks
Known partner devices
AlarmText_CS
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Enable alarm info (input)
Possible partner function blocks
Known partner devices
EnableAlarmInfo
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Error code
English
4910
RXB room temp. sensor error
4930
RXB room air condensation
4960
RXB general fault
4970
RXB PPS fault
For more information on the alarm concept, refer to "Communication via bus, Synco700
& RXB", CE1P3127.
10.14 Reset setpoint shift
When the system changes from
Comfort
or
Precomfort
to
Economy
or
Protection
, the
setpoint shift can be reset (see page 72). This function can be enabled and disabled via
Central functions.
The setpoint shift can only be reset with the QAX34.1 and QAX84.1 room units, which
have an LCD display. Enabling this function in room units with a mechanical setpoint
shift (potentiometer) causes data transmission errors.
HandyTool
Parameter Short
name
Range
Basic setting
*137
Reset setpoint shift
0 = Disabled
1 = Enabled
Disabled
KNX
R
CO
Display on Synco
device:
STOP
Important!