37/140
Siemens
RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Room operating modes
28 Feb 2009
The presence detector has two states:
State
Description
Occupied
•
Room is occupied.
•
Room controller switches to
Comfort.
Unoccupied
•
Room is not occupied.
•
Room controller switches to
Economy or Precomfort.
The table below shows
Effective occupancy
as a function of the
occupancy
time
schedule and the presence detector.
Rule: Occupied takes precedence over unoccupied. If
either
the schedule
or
the
presence detector transmits
occupied
, the room is
occupied.
Presence detector
Occupancy schedule
Effective
occupancy
No schedule.
Occupied.
Occupied.
Occupied.
Standby.
Standby.
No presence detector
Unoccupied.
Unoccupied.
No schedule.
Unoccupied.
Occupied.
Occupied.
Standby.
Standby.
Unoccupied
(no people
present).
Unoccupied.
Unoccupied.
No schedule.
Occupied.
Occupied.
Occupied.
Standby.
Occupied.
Occupied
(people present).
Unoccupied.
Occupied.
•
The Effective
room operating mode
can be changed by the Effective
occupancy
only
during the building-in-use period (defined by the
Use
schedule).
•
The change in the
Effective room operating mode
is event-driven at exactly the time
when the
Effective occupancy
changes.
•
The room unit or
Temporary Comfort mode
(both priority 3) can cause the
Effective
room operating mode
to change again
Æ
last command wins.
Effective occupancy
Effective room operating
mode
Æ
Occupied.
Comfort.
Æ
Standby.
Precomfort.
Æ
Unoccupied.
Economy.
Key:
Æ
Occupied means: "changes to occupied ".
The following S-mode communication object is used for schedule usage
from a building
automation and control system:
Time scheduler
Occupancy
(input communication
object)
Flags
R W C T U
Type Receive
timeout
States
0 1 1 0 0 20.003
DPT_OccMode
Yes
0 = Occupied
1 = Standby
2 = Unoccupied
Effective occupancy
Effective room operating
mode
KNX
R
CO