RXB (KNX) Applications library
CLC and RAD description of functions for CC-02 CM110384en_03
Building Technologies
Select communications mode
28 Feb 2009
3.3
Implement application example
The Synco
TM
planning and commissioning protocol C3127 enables you to clearly draw
plant and necessary communication settings.
Proceed as follows:
1.
Enter general information such as plan name, device name, device types,
applications, etc..
2.
Copy the device addresses for the bus members along with the basic settings for
communication from the building floor plan.
3.
Enter the geographical zone addresses as per the defined groups.
The following example shows the completed protocol for the plant of
Sport AG:
Possible settings
RMU RMH RMK OZW RMB
RXB QAW
1
2
3
4
5
6
7
Plant
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Sport Ltd
Room number
309
307
308
308
308
Device name
X
X
X
-
X
X
-
Reception
Conference
Reception
Office
Office
Office
Office
Device type
RMU
7..
RMH,
RMZ
RMK
OZW
771...
RMB
795
RXB
....
QAW
740
RMB795
RXB..
RMB795 [2] RXB..
RXB..
RXB..
RXB..
Plant type
X
X
X
-
X
X
-
B
FC03
FC03
FC03
FC03
FC03
KNX-ID (Example ID: 00FD000016D5)
X
X
X
X
X
X
X
Area [ 0...15 ] . Line [ 1; 2...15 ] .
Device address [1..253;
255
]
X
X
X
X
X
X
X
0.2.10
0.2.114
0.2.110
0.2.111
0.2.112
0.2.113
Decentral bus power supply [ Off,
On
]
X
X
X
-
X
-
-
Aus
Clock time operation [
Autonomous
, Slave, Master ]
X
X
X
X
X
-
-
Autonom
Remote setting chlock slave [ No,
Yes
]
X
X
X
X
X
-
-
Nein
Remote reset of fault [
No
, Yes ]
X
X
X
-
X
-
-
Nein
Geographical zone (Apartment.Room.Subzone)
(A.R.S) [
1
...126 ].[ 1...63 ]. [1]
X
2
2X
X
-
10X
X.X.1
X
1.1.1
1.1.1
2.1.1
2.1.1
2.2.1
2.3.1
2.4.1
(with own room sensor)
X
1
2X
X
-
-
X
X
X
----
X
X
X
Time switch operation [
Autonomous
, Slave, Master ]
X
1
2X
X
-
-
-
-
Time switch slave (apartment) [
1
...126 ] . 1 . 1
X
1
2X
X
-
-
X.1.1
-
1.1.1
2.1.1
2.1.1
2.1.1
2.1.1
Temperature control [
Master
, Slave ]
-
-
-
-
-
X
-
Master
Master
Master
Master
Master
* Control strategy [
Caskade
, Constant, Alternating ]
X
4
-
-
-
-
-
-
** Combination of room control [
Master
,
Slave external setpoint , Slave internal setpoint ]
-
2X
X
-
-
-
-
Room group (name)
-
-
-
-
10X
-
-
Conference
Office
QAW operation zone (apartment) [ ---,
1
...126 ] . 1 . 1
-
-
-
-
10X
-
-
Information
Room /
Room group
Basic settings
Room group Conference
Apartment = 1
Room group Office
Apartment = 2
1
2
3
Upon commissioning, enter the settings for the same-name data points in the devices
according to the created list.
Procedure for planning
Example for
Sport Ltd.
Implementation upon
commissioning