Siemens DB-HR Installation Instructions Download Page 1

P/N 315-033220-5

DETECTOR AND BASE PLACEMENT

Detector and base locations shall follow the drawings provided or approved
by Siemens Industry, Inc. or its authorized distributors. This is extremely
important! The detector placements shown on these drawings were chosen
after a careful evaluation of all facets of the protected area. When drawings
are not available, refer to 

Detector Placement

 section of detector Installation/

Wiring Instructions and to NFPA 72, National Fire Alarm Code and CAN/ULC-
S524.

BASE WIRING

The Model DB-HR from Siemens Industry, Inc. is a polarity insensitive detector
base and works with HFP-11, HFPT-11, HFPO-11, SFP-11*, SFPT-11* and SFPO-
11* detectors only. Detectors should be interconnected as shown in Figure 1
and wired to the DLC (refer to DLC Installation Instructions, P/N 315-033090), FS-
DLC (refer to FS-250 Installation, Operation and Maintenance Manual, P/N 315-
049353) or FDLC (refer to FS-250C Installation, Operation and Maintenance
Manual, P/N 315-049589C), as applicable. Line 1 and Line 2 can be either line of
the loop. 

Note any limitations on the number of detectors and restrictions

on the use of remote devices permitted for each circuit.

Figure 1

DB-HR Wiring Diagram Using HFP-11 Series and SFP-11 Series Detectors

Siemens Industry, Inc.
Building Technologies  Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

*THE RELAY CONTACTS ARE

SHOWN IN THE NON-ALARM/

SYSTEM RESET CONDITION.

LINE 1 AND LINE 2 CAN BE EITHER LINE OF THE LOOP.

DO NOT USE AN END

OF LINE DEVICE

TO NEXT DEVICE

DO NOT USE AN END

OF LINE DEVICE

TO NEXT DEVICE

5

NO

NC

C

6

TO INITIATING CIRCUIT

OF SIEMENS INDUSTRY,

INC. CONTROL PANEL

REMOTE RELAY BASE

MODEL DB-HR

LINE 1

LINE 2

LINE 1

LINE 2

RELAY*

CONTACTS

3A, 120 VAC

3A, 30 VDC

DB-HR RELAY BASE

Detector Base

Installation Instructions
Model DB-HR

*SFP-11, SFPT-11 and SFPO-11 detectors are approved for use in Canada only.