![Siemens CPU 312 Hardware And Installation Manual Download Page 94](http://html.mh-extra.com/html/siemens/cpu-312/cpu-312_hardware-and-installation-manual_375984094.webp)
:LULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
7-8
A5E00105492-03
1RWH
The PS 307 power supply module is equipped with two additional DC 24 V
connections (L+ and M) for the supply of I/O modules.
:LULQJ)URQW&RQQHFWRUV
,QWURGXFWLRQ
The front connector is used to connect the sensors and actuators of your system to
the S7-300 PLC. Wire the sensors and actuators to this front connector and then
plug it into the module.
)URQWFRQQHFWRUYHUVLRQV
Front connectors come in 20-pin and 40-pin versions, each with screw contacts or
spring terminals. 40-pin front connectors are required for CPUs 31xC and
32-channel signal modules.
You must use the following front connectors, depending on the module:
Table 7-4
Assignment of front connectors to modules
0RGXOH
)URQWFRQQHFWRUVZLWK
VFUHZWHUPLQDOV2UGHU
1R
)URQWFRQQHFWRUVZLWK
VSULQJWHUPLQDOV2UGHU
1R
Signal modules
(not 32-channel),
Function modules,
Communication module
CP 342-2
6ES7 392-1AJ00-0AA0
6ES7 392-1BJ00-0AA0
Signal modules
(32-channel) and
CPU 31xC
6ES7 392-1AM00-0AA0
6ES7 392-1BM01-0AA0
7HUPLQDWLRQZLWKVSULQJWHUPLQDOV
To terminate a conductor in a front connector with spring terminals, simply insert
the screwdriver vertically into the opening with the red opening mechanism, insert
the wire into the terminal and remove the screwdriver.