S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
5-14
A5E00105492-03
([DPSOH6HOHFWLQJD&DELQHW
,QWURGXFWLRQ
The sample below clearly shows the maximum permitted ambient air temperature
at a specific power loss for different cabinet designs.
$VVHPEO\
The following device configuration should be installed in a cabinet:
•
Central unit, 150 W
•
Expansion modules, each with 150 W
•
Load power supply under full load, 200 W
This results in a total power loss of 650 W.
3RZHUORVVGLVVLSDWHG
The diagram in the figure below shows guide values for the permitted ambient air
temperature of a cabinet with the dimensions 600 mm x 600 mm x 2,000 mm,
depending on power loss. these values only apply if you maintain the specified
installation and clearance dimensions for racks (rails).