![Siemens CPU 312 Hardware And Installation Manual Download Page 33](http://html.mh-extra.com/html/siemens/cpu-312/cpu-312_hardware-and-installation-manual_375984033.webp)
&RQILJXULQJ
S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-7
$UUDQJLQJ0RGXOHVRQD6LQJOH5DFN
$UH\RXXVLQJRQHRUPRUHUDFNV"
The number of racks you need will depend on your application.
5HDVRQVIRUXVLQJDVLQJOHUDFN
•
Compact, space-saving use of all your modules
•
Centralized use of your modules
•
Fewer signals to be processed
5HDVRQVIRUGLVWULEXWLQJPRGXOHVEHWZHHQVHYHUDOUDFNV
•
More signals to be processed
•
Insufficient slots available
7LS
:
If you opt for installation on a single rack, insert a dummy module to the right of the
CPU (order no.: 6ES7 370-0AA01-0AA0). This gives you the option of inserting a
second rack for your application in the future, simply by replacing the dummy
module with an interface module and without having to reinstall and rewire the first
rack.
5XOHV$UUDQJLQJPRGXOHVRQDVLQJOHUDFN
The following rules apply to single-rack module installations:
•
No more than eight modules (SM, FM, CP) may be installed to the right of the
CPU.
•
All modules mounted on a rack must not consume more than a total of 1.2 A
from the S7-300 backplane bus.
7KHSRZHUFRQVXPSWLRQRIPRGXOHV
is listed under the technical data, e.g.
60RGXOH'DWD5HIHUHQFH0DQXDO
or in
the
5HIHUHQFH0DQXDO
for your CPU