Use Cases
590
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
E.3
Usage as Telecontrol Substation with Integrated Switch
for External System Connection
Features
•
Communication with the control system via IEC 60870-5-104
(Ethernet-Interface, X1 or X4, can be set by parameter)
•
Communication with the external system via IEC 60870-5-104
(Ethernet interface, X1 or X4, can be set by parameter)
•
CP-8000, CP-8021 or CP-8022 is used as switch between control system and external
system
•
1 IP address
•
1 subnet mask
•
1 default router
•
Parameter
Network settings | IP address | Mode of Ethernet Ports
=
1 IP address (connected ports in switch mode)
(in this case both Ethernet interfaces use the MAC address of X1)
Office Zone
X4
X1
Router
E SC
CP-8000
CP-8021
CP-8022
Control Center
IP address
172.16.0.4
255.255.0.0
172.16.0.254
Subnet mask
Default router
PREx / ET84
IP address
Subnet mask
Default router
172.16.0.3
255.255.0.0
172.16.0.254
IP address
172.17.0.22
Subnet mask 255.255.0.0
IP address
172.16.0.254
External
device
Substation Zone
Control Center Zone