Engineering via SICAM WEB
340
Unrestricted
SICAM A8000 / CP-8000 • CP-8021 • CP-8022 Manual
DC8-037-2.02, Edition 10.2017
9.1.7.2 Physical Interface for the Communication
CP-8000/CP-802
x
can communicate simultaneously via multiple physical interfaces. For each
configured protocol element an interface must be assigned exclusively.
The assignment of the interface for each protocol element resides in the directory tree under
SICAM A8000 CP-80xx | Master module | PRE
<0…3>
:
<protocol>
| Common settings
.
Equipable protocols can be assigned with the parameter
Interface
:
Firmware
Protocol name
X1
X2
X3
X4
X6
X7
103MT0
IEC 60870-5-103 Master
-
ü
ü
-
ü
-
BPPT0
IEC 60870-5-101 point-to-point
-
ü
ü
1)
-
ü
-
DIAST0
Dial-up traffic Slave
-
ü
-
-
ü
3)
-
ET83
IEC 61850 Ed. 1 (Client, Server, GOOSE)
ü
2)
-
-
ü
2)
-
-
ET84
IEC 60870-5-104
ü
2)
-
-
ü
2)
-
ü
ET85
IEC 61850 Ed. 2 (Client, Server, GOOSE),
Ed. 1 (Client)
ü
2)
-
-
ü
2)
-
-
UMPMT0
IEC 60870-5-101 Master
-
ü
ü
-
ü
-
UMPST0
IEC 60870-5-101 Slave
-
ü
ü
-
ü
-
AGPMT0
AGP interfacing Master
-
ü
ü
-
ü
-
BMCUT0
Benning MCU ASCII protocol
-
ü
ü
2)
-
ü
-
COUMT0
IEC 62056-21 (IEC 1107) Master
-
ü
ü
-
ü
-
DNPST0
DNP3 Slave
-
ü
ü
-
ü
-
DNPMT0
DNP3 Master
-
ü
ü
-
ü
-
DNPiT1
DNP3 TCP/IP Slave
ü
2)
-
-
ü
2)
-
-
DNPiT2
DNP3 TCP/IP Master
ü
2)
-
-
ü
2)
-
-
MODMT2
MODBUS RTU Master
-
ü
ü
-
ü
-
MODST0
MODBUS RTU Slave
-
ü
ü
-
ü
-
PCBST0
SAT SK 1703 PCMBA Slave
-
ü
ü
-
ü
-
RP5UT1
ABB RP570/571 Slave
-
ü
ü
-
ü
-
SMST0
ASCII protocol for SMS alerting
-
ü
-
-
ü
3)
-
ST1ST0
Siemens SINAUT ST1 Slave
-
ü
ü
-
ü
-
TG8ST0
L&G Telegyr 800 Slave
-
ü
ü
-
ü
-
1)
only in RS-422 mode
2)
fixed if
Mode of ethernet ports
=
1 IP address (connected ports in switch mode)
3)
only in RS-232 mode