4 Mode of Operation
4.2 PLC data types
HCS4x00Library
Entry ID: 109478117, V2.2.1, 09/2018
30
S
ie
m
e
n
s
A
G
2018
A
ll r
ig
h
ts
r
e
s
e
rv
e
d
4.2.32
"LHcs4x00_typeDs202Value"
The “LHcs4x00_typeDs202Value” PLC data type includes the measured values of
the PM4000 U/I (only for plugged and configured PM4000 U/I).
Table 4-32
Name
Data
type
Description
frequency
Int
Frequency (with one decimal place)
voltageL12
Int
Voltage reading L1/L12 (in [V] with one decimal place)
voltageL23
Int
Voltage reading L2/L23 (in [V] with one decimal place)
voltageL31
Int
Voltage readings L3/L31 (in [V] with one decimal place)
currentRmsL12
Int
Measured current RMS L1/L12 (in [A] with three decimal points)
currentRmsL23
Int
Measured current RMS L2/L23 (in [A] with three decimal points)
currentRmsL31
Int
Measured current RMS L3/L31 (in [A] with three decimal points)
currentL12
Int
Mean measured current L1/L12 (in [A] with three decimal points)
currentL23
Int
Mean measured current L2/L23 (in [A] with three decimal points)
currentL31
Int
Mean measured current L3/L31 (in [A] with three decimal points)
powerRmsL12
Int
Power RMS L1/L12 (in [W] with one decimal place)
powerRmsL23
Int
Power RMS L2/L23 (in [W] with one decimal place)
powerRmsL31
Int
Power RMS L3/L31 (in [W] with one decimal place)
powerNominalL12
Int
Mean power L1/L12 (in [W] with one decimal place)
powerNominalL23
Int
Mean power L2/L23 (in [W] with one decimal place)
powerNominalL31
Int
Mean power L3/L31 (in [W] with one decimal place)
4.2.33
"LHcs4x00_typeDs203"
The “LHcs4x00_typeDs203” PLC data type includes the data of data record 203
“measured values POM4220 Highend" (only for plugged and configured POM4220
Highend).
Table 4-33
Name
Data type
Default
value
Description
valid
Bool
false
Validity
pom
Array[1..24] of
"LHcs4x00_typeDs203Pom"
Array with the measured values of the
POMs4220 Highend
4.2.34
"LHcs4x00_typeDs203Pom"
The “LHcs4x00_typeDs203Pom” PLC data type includes the measured values of
the POM4220 Highend (only for plugged and configured POM4220 Highend).
Table 4-34
Name
Data type
Description
actualCurrentChannel
Array[1..8] of Int
Array with the current per channel in ampere (A) with two
decimal points
actualLoadChannel
Array[1..8] of Int
Array with the performance per channel in watts (W)
reserved
Array[1..4] of Int
reserved