1-33
Description
FP-11 Intelligent/Analog
Photoelectric Detector
1
The FP-11 is an intelligent/analog
photoelectric detector that can be used
as an area or duct detector [FP-11(d)].
It uses either a DB-11 low profile
mounting base or DB-3S mounting
base with the DB-ADPT adapter, a
DB-X11RS mounting base with relay
or DB-X3RS mounting base with relay
with the DB-ADPT adapter, an ADBI-60
audible base with the DB-ADPT adapter,
or an AD-11P or AD-11XPR air duct
housing. The FP-11 requires MXL Rev
10.0 or higher firmware.
FPT-11 Intelligent Thermal Detector
The FPT-11 is an intelligent/analog rate-
compensated/fixed-temperature type
thermal and photoelectric detector. It
can only be used as an area detector. It
uses either a DB-11 low profile mount-
ing base or DB-3S mounting base with
the DB-ADPT adapter, a DB-X11RS
mounting base with relay or DB-X3RS
mounting base with relay with the
DB-ADPT adapter, or an ADBI-60
audible base with the DB-ADPT adapter.
The FPT-11 requires MXL Rev. 10.0 or
higher firmware.
ID-60P Intelligent/Analog
Photoelectric Detector
1
The ID-60P is an intelligent/analog
photoelectric detector that can be used
as an area or duct detector [ID-6OP(d)].
It uses either a DB-3S low profile
mounting base, a DB-X3RS mounting
base with relay, an AD-3P duct hous-
ing, or an ADBI-60 audible base.
ID-60PT Intelligent/Analog Photo-
electric Detector with Heat Sensor
1
The ID-60PT is an intelligent/analog
rate-compensated/fixed-temperature
type thermal and photoelectric detec-
tor. It can only be used as an area
detector. It uses either a DB-3S low
profile mounting base, a DB-X3RS
mounting base with relay, or an
ADBI-60 audible base.
ID-60I Intelligent/Analog lonization
Detector
1
The ID-60I is an intelligent/analog
ionization detector for use in open
areas at altitudes of 0 to 4000 feet. It
uses either a DB-3S low profile mount-
ing base, a DB-X3RS mounting base
with relay, or an ADBI-60 audible base.
ID-60IH Intelligent/Analog lonization
High Altitude Detector
1
The ID-60IH is an intelligent/analog
ionization detector for use in open areas
at altitudes of 3000 to 8000 feet. It uses
either a DB-3S low profile mounting
base, a DB-X3RS mounting base with
relay, or an ADBI-60 audible base.
ID-60IA Intelligent/Analog lonization
High Air-Velocity Detector
1
The ID-60IA is an intelligent/analog
ionization high air-velocity detector for
use in open areas, computer facilities,
and air ducts at altitudes of 0 to 4000
feet, with air velocities of 0 to 1200
feet per minute. It uses either a DB-3S
low profile mounting base, a DB-X3RS
mounting base with relay, or an
ADBI-60 audible base.
Analog
Addressable
Devices
NOTES
1. Refer to Appendix F,
Envirolink
2. Refer to Appendix I,
Application Specific
Detection (ASD)
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...