3-8
Operation
How to Individually Acknowledge a
Supervisory (NFPA 72 Proprietary,
UL 1076
)
Press
SUPV ACK.
The System
acknowledges the supervisory
displayed and then displays the
next unacknowledged supervisory.
If your system has a printer, it prints
an acknowledgment message
similar to the following:
ACK Supervisory 1-5 12:01:28 Dec 31,20xx
#2 [custom message], [device type]
Note that the acknowledgment
message includes the term ACK
to indicate this supervisory was
acknowledged.
Continue acknowledging super-
visories as explained above until
the System displays the following
message:
ALL SUPERVISORIES ACKNOWLEDGED
The
SUPERVISORY
LED glows
steadily to indicate that all super-
visories are acknowledged. If there
are no troubles or security condi-
tions still in the System, the internal
audible goes silent; if any of those
conditions still exist, the internal
audible pulses.
If your System includes a printer, it
prints the following message:
ACK Supervisory 12:05:44 Dec 31,20XX
All Supervisories Are Now Acknowledged.
How to Block Acknowledge a
Supervisory (NFPA 72 Local,
72 Municipal Tie, 72 Remote Station)
Note the specific location of the
supervisories by using the
procedures described above.
Unlock and open the door.
Press
SUPV ACK
to acknowledge
all
supervisories. The System
displays the following message:
ALL SUPERVISORIES ACKNOWLEDGED
If your System includes a printer,
it prints the following message:
ACK Supervisory 11:59:59 Dec 31,20xx
All Supervisories Are Now Acknowledged.
If you press
SUPV ACK
again,
the System displays:
ALL SUPERVISORIES ACKNOWLEDGED
The
SUPERVISORY
LED glows
steadily to indicate that all super-
visories are acknowledged. If there are
no troubles or security conditions in
the System, the internal audible goes
silent; if any of those conditions still
exist, the internal audible pulses.
Trouble
How the System Annunciates Troubles
When a trouble is detected, the Sys-
tem causes the
TROUBLE
LED on the
MKB to flash, the Systems internal
audible to sound, and the alphanumeric
display on the MKB to alternate in a
sequence among the three messages
shown below. This example assumes
that two troubles were received:
Message 1:
1-001 [custom message]
002 [trouble type]
IN TBL
Technical Manuals Online! - http://www.tech-man.com
firealarmresources.com
Summary of Contents for Cerberus PYROTRONICS MXL
Page 167: ...3 68 Operation Technical Manuals Online http www tech man com firealarmresources com ...
Page 309: ...A 2 Appendix A Technical Manuals Online http www tech man com firealarmresources com ...
Page 311: ...B 2 Appendix B Technical Manuals Online http www tech man com firealarmresources com ...
Page 321: ...F 4 Appendix F Technical Manuals Online http www tech man com firealarmresources com ...
Page 323: ...G 2 Appendix G Technical Manuals Online http www tech man com firealarmresources com ...
Page 325: ...H 2 Appendix H Technical Manuals Online http www tech man com firealarmresources com ...
Page 329: ...J 2 Appendix J Technical Manuals Online http www tech man com firealarmresources com ...
Page 343: ...L 2 Appendix L Technical Manuals Online http www tech man com firealarmresources com ...
Page 355: ...Glossary 4 Glossary Technical Manuals Online http www tech man com firealarmresources com ...
Page 363: ...Index 8 Index Technical Manuals Online http www tech man com firealarmresources com ...