Mounting/Installation
Mount and install PN1002-A1
4
46 | 122
A6V11899867_en--_a
4.14 Mount and install PN1002-A1
The 'RS485 module (1 port)' PN1002-A1 provides an isolated 'PACE-Bus' (RS485)
connection, an isolated 24 V with integrated ground fault detection, and connectors
for isolated analog audio inputs and outputs.
One PN1002-A1 can be mounted on the Cerberus PACE Compact audio matrix
board in the options area.
Mount the PN1002-A1 on position 'UI1' on the digital audio matrix board. Plug the
PN1002-A1 to the connectors 'UI1-A' and 'UI1-B'. Fasten it with the 2 enclosed
screws to the studs (marked in red circles)
Fig. 21: Mount PN1002-A1
Connect the analog audio input from the PN1002-A1 to the digital audio matrix
board. Use an enclosed cable to connect 'UI1-C' (to intern 'Audio In') with the
required analog audio input. See
If required to connect the analog audio output from the PN1002-A1 to the digital
audio matrix board, use an enclosed cable to connect 'UI1-D' (from intern 'Audio
Out') with the required analog audio output. See
Connector 'UI1-C' on the digital audio matrix board
Pin
Description
Remark
1
Signal out +
Analog audio out +
2
GND
Reference GND
3
Signal out -
Analog audio out -
Table 15: Connector 'UI1-C' on the digital audio matrix board
Connector 'UI1-D' on the digital audio matrix board
Pin
Description
Remark
1
Signal in +
Analog audio in +
2
GND
Reference GND
3
Signal in -
Analog audio in -
Table 16: Connector 'UI1-D' on the digital audio matrix board
An external call station can be connected via the single wire terminal 'CN1' on the
front of the PN1002-A1 or via a RJ45 plug 'J4' on the rear.