Mounting/Installation
Mount and install additional power amplifiers
4
36 | 122
A6V11899867_en--_a
4.7.2 Mount and install additional power amplifiers on
PC1002
Only the 'Power amplifier (1x500W)' PV1002-A1 can be mounted in the 'Voice
alarm panel Compact 1000' PC1002-A3 cabinet. Other amplifier types are not
allowed.
The power amplifiers PV1002-A1 are mounted in the amplifier mounting area. They
are connected to the audio matrix board in the amplifier connecting area. Up to 6
PV1002-A1 can be mounted in one PC1002-A3 cabinet.
NOTICE
Make sure that the 230 V and the batteries are both disconnected before the
power amplifiers PV1002-A1 are mounted.
Fig. 9: PC1002-A3 power amplifiers connection overview
To mount the power amplifier in the amplifier mounting area, the pre-assembled
power supply must be removed by following the steps below:
1.
Disconnect all the wiring from the power supply.
2.
Unscrew the 4 screws on the power supply.
3.
Take out the power supply.
There are 2 amplifiers pre-mounted on position 'Amp 1' and 'Amp 2'. The additional
amplifiers are mounted on the selected position in the amplifier mounting area.