4.7 Mount and install additional power amplifiers
4.7.1 Mount and install additional power amplifiers on
PC1001
Only the 'Power amplifier (1x200W)' PV1001-A1 can be mounted in the 'Voice
alarm panel Compact 400' PC1001-A3 cabinet. Other amplifier types are not
allowed.
The power amplifiers PV1001-A1 are mounted in the amplifier mounting area. Up
to 6 PV1001-A1 can be mounted in one PC1001-A3 cabinet.
There are 2 amplifiers pre-mounted on position 'Amp 1' and 'Amp 2'. The additional
amplifiers are mounted on the selected position. Each one is fixed with 2 screws.
The amplifier on position 'Amp 5' is used as the pilot tone amplifier. The amplifier
on position 'Am
p 6' is used as a backup amplifier. These two amplifiers can’t be
used as regular amplifiers with speaker lines connected.
Fig. 8: PC1001-A3 mount power amplifiers
NOTICE
Plug the enclosed jumpers to the correct connectors
The amplifiers do not work without jumpers.