Mounting/Installation
Wire the mains supply line
4
A6V11899867_en--_a
31 | 122
4.5.1 Mains connection PC1001
The 230 V mains connector of the 'Voice alarm panel Compact 400' PC1001-A3 is
in the upper right of the cabinet. The power supply and the PE in the cabinet are
already pre-assembled.
Fig. 4: PC1001-A3 mains connector with pre-assembled wiring
Connection to the power supply; pre-assembled
PE connection to the cabinet; pre-assembled
'X100'
Terminal block for the mains supply connection
Mains connector - 'X100'
Pin
Designator Connection
Color
Description
1
L1
Outer conductor
Brown
Mains connection
2
L1
Outer conductor
Brown
Pre-assembled; power supply
3
N
Neutral conductor
Blue
Mains connection
4
N
Neutral conductor
Blue
Pre-assembled; power supply
5
PE
Protective conductor
Yellow/green
-
6
PE
Protective conductor
Yellow/green
Pre-assembled; power supply
7
PE
Protective conductor
Yellow/green
-
8
PE
Protective conductor
Yellow/green
Pre-assembled; cabinet
9
PE
Protective conductor
Yellow/green
-
10
PE
Protective conductor
Yellow/green
-
11
PE
Protective conductor
Yellow/green
Mains connection
12
PE
Protective conductor
Yellow/green
Pre-assembled; cabinet
Table 1: PC1001-A3 mains connector - 'X100'
Follow the steps below to wire the mains supply line:
1.
Connect the protective conductor with the yellow/green wire to the free 'PE'
ground terminal.
2.
Connect the blue neutral conductor to the terminal 'N'.
3.
Connect the brown outer conductor to the terminal 'L1'.
Summary of Contents for Cerberus PACE Compact
Page 12: ......