B2F020 Converter
69
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
13 B2F020
Converter
13.1 Overview
z
Converts the
Mains
voltage to the
system
voltage
z
Consistent with the battery-charging function units E3X10. and E3C...
z
Designed for an output current of 6 A at 29.6 VDC
z
Requires no special cooling
z
Built-in thermal fuse
z
Current limited
z
Short circuit proof
z
Parallel operation
z
Switches on primary side
z
With metal shielding
z
Dimensions 200 x 100 x 40 mm
Power supply general
The power supply for the CS1140 series of fire detection system control units con-
sists of the following three components:
–
Converter
B2F020
–
Battery-charging function unit
either as an integrated component in the
E3X10. (for details see E3X10.) or as a separate battery-charging module E3C...
(for details see E3C...)
–
Emergency power battery
, capacity according to quiescent current and the re-
quired mains autonomy; see document 1076 (EP5), 008725 (EP7F-Z1) ”Emer-
gency power calculation”)
Over voltage protection
Additional surge protectors are only necessary in
Special cases
e.g. where there
is a particular risk from lightning, overhead mains lead etc. (see Z3I041, Z3I121 –>
page 76)
13.2 Key
data
Mains voltage
115 / 230 VDC +10 %/–15 % 50...60Hz
Power consumption
40...320 VA
Mains fuse
3.15 A/T, permanently integrated, not exchangeable on site
Output current
max. 6 A continuous (limited)
Output voltage
29.6 VDC
+/–2 %
Residual ripple
max. 300 mVpp
Quiescent current with battery operation 0 mA
Temperature range
0...+70 °C without ventilator,
automatic switch-off at > 90 °C
Standard
CE / prEN54-4