E3M111 Line module ”AnalogPLUS” (supersedes E3M110)
103
Building Technologies
001260_k_en_--.doc
Fire Safety & Security Products
02.2005
7
Fuses:
'F19/F20'
1 A/F Supply voltage for DC modules (SMD fuses
can only be changed at factory)
8
Fuses:
'F1...F16'
1 A/F Lines 1..4 SMD fuses (can only be changed at
factory)
24.5 Connections
to other I-Bus modules
from previous I-Bus modules
Data communication
I-Bus modules
Double flat cable header
ST1
to other I-Bus modules
red
green
blue
blue
Supply for
I-Bus modules
Plug-in terminals
K1
from previous I-Bus modules
Supply voltage for DC-modules
24V/max. 500mA,not monitored
DS11 AnalogPLUS detector
Max. 128 addresses
Module chassis ground
Line 4
AnalogPLUS detector
Loop or stub line
Module chassis ground
Line 3
AnalogPLUS detector
Loop or stub line
Line 2
AnalogPLUS detector
Loop or stub line
DS11 AnalogPLUS detector
Max. 128 addresses
Line 1
AnalogPLUS detector
Loop or stub line
Terminal block
X10
E3M111
1
2
3
4
5
6
7
8
9
10
11
12
+
-
+
-
+
-
+
-
+
-
+
13
14
15
16
-
+
-
17
18
19
20
+
-
F2
F1
F4
F3
F6
F5
F8
F7
F10
F9
F12
F11
F14
F13
F16
F15
2
3
4
+
+
1
24V
5V
With loop line:
Feedback
With loop line:
Feedback
With loop line:
Feedback
With loop line:
Feedback
F17
F18
for special applications only
- open collector per line for ext. LED
- active upon emergency alarm
Mimic display
Flat cable header (Mini)
ST10
DC..
24V
F20
F19
+
-
GND
-
-
≥
EP7F, wire the unused lines as loop line
(connect to chassis ground)
Pin assignment ST10
Pin
Line
GND
GND
GND
GND
1
2
3 4
5
6
7
8
9 10 11 12
1
2
3 4
26
P
in
26
P
in
12 P
in