L
OOP
D
ETECTOR
H
ANDBOOK
667/HE/20663/000
Issue 13
Page 14
2.5.1
Siemens ST4R / SLD4 Detectors
FACILITY
SHAPE
NO.OF
NO.OF
MAX
LANES
TURNS
FEEDER
V/A
Chevron/Diamond 1 to 3
3
300 m
V/A
Chevron/Diamond 4
3
250 m
V/A
Chevron/Diamond 5
3
200 m
V/A
Chevron/Diamond 6
3
150 m
SDE/SA
Rectangle
1
3
300 m
SDE/SA
Chevron
1
3
300 m
COUNT/QUEUE
Rectangle
1
3
600 m*
SCOOT
Rectangle
1 or 2
3
600 m*
MOVA
Diamond
1 to 3
3
300 m
MOVA
Diamond
1 to 3
3
600 m*
Note:
* = Not cycle sensitive
2.5.2
Peek/Sarasota and Microsense MXED Detectors
FACILITY
SHAPE
NO.OF
NO.OF
MAX
LANES
TURNS
FEEDER
V/A
Chevron/Diamond 1 to 3
3
300 m
V/A
Chevron/Diamond 4
3
250 m
V/A
Chevron/Diamond 5
3
200 m
V/A
Chevron/Diamond 6
3
150 m
SDE/SA
Rectangle
1
3
300 m
SDE/SA
Chevron
1
3
300 m
COUNT/QUEUE
Rectangle
1
3
300 m
SCOOT
Rectangle
1 or 2
3
300 m
Note:
Sarasota MTS 36ZE and MTS 38ZE (667/7/21031/102 and /104)
detectors have a built-in extension timer and must
not
be used with
Traffic Signals.
2.5.3
Plessey ST and Microsense MSE Detectors
Note:
These detectors are now obsolete. The following is included for
information only.
FACILITY
SHAPE
NO.OF
NO.OF
MAX.
LANES
TURNS
FEEDER
V/A
Chevron/Diamond 1 to 4
3
150 m
V/A
Chevron/Diamond 5 to 6
3
100 m
SDE/SA
Rectangle
1
3
150 m
SDE/SA
TBA
1
TBA
TBA
COUNT QUEUE
Rectangle
1
3
150 m
SCOOT
Rectangle
1 or 2
3
150 m