BC8001A Installation and Operating Instruction
Page 26/49
11.2 How to isolate/open
Isolate/Open Line
Function:
This is only necessary in exceptional situations, for example, while some part of
the construction is in process. As soon as conditions have returned to normal, the isolated
line must be immediately restored to normal status again.
Status:
LCD will display isolation event automatically as “Isolation Screen”.
The isolation LED is on.
The buzzer sounds.
How to isolate/open line:
1. Press “ ” to enter main menu.
The main menu is displayed.
2. Press “
↓
” to choose “3.Operation” and press “OK” key.
All stations are displayed.
3. Press “
↓
” to choose one station which include the desired line and press “OK” key.
4. Press “
↓
” to choose “Line” and press “OK” key.
All lines are displayed.
5. Press “
↓
” to choose one desired line and press “OK” key.
6. Press “
↓
” to choose “2.Isolate” / ”3.Open” and press “OK” key.
Isolation status is shown/disappeared.
Isolation Screen
<Operate Stations > L3 A
001 BC8001A Compact Stati
<Operate Stations > L3 A
1.Line
2.System Property
<Operate Lines > L3 A
001 BC8001A IOs
002 BC8001A Ports
003 BDS Line
004 BC8001A Powers
<Operate Lines > L3 A
1. Points
2. Isolate
3. Open
4. Test
<Main Menu> L 3 A
1. RT Information
2. History Record
3. Operation
4. Configure
<RT – Isolation:1> L1 A
- 1 Room 102 heat detector