![Siemens Argus 7SR11 Manual Download Page 297](http://html.mh-extra.com/html/siemens/argus-7sr11/argus-7sr11_manual_382648297.webp)
7SR11 & 7SR12 Commissioning and Maintenance Guide
©2017 Siemens Protection Devices Limited
Chapter 6 Page 13 of 72
polarising reference voltage is set to 0deg and the current phase angle is measured with respect to this
reference.
Alternatively, the instrument can be checked at the 4 points marked a,b,c & d on Figure 2-1 only.
Forward
Reverse
Lag (point C)
Lead (point A)
Lead(point B)
Lag (point D)
Pick-up
Drop-off
Pick-up
Drop-off
Pick-up
Drop-off
Pick-up
Drop-off
MTA
MTA-85
MTA+85
MTA-85
MTA-85
Phase A
Phase B
Phase C
V
C
V
B
V
A
I
A
With balanced 3-phase system quantities:
Adjust the phase angle of the currents
relative to the voltages:
Verify directional pick-up and drop off at
points A, B, C and D
Alternatively,
Verify correct directional indication at points
a, b, c and d (C.A +75
0
, +95
0
, -75
0
, -95
0
)
A
B
D
C
a
d
b
c
FWD
REV
+60
0
+30
0
0
0
+270
0
+180
0
+210
0
+240
0
+90
0
V
BC
Figure 2-1
Directional Phase Fault Boundary System Angles
5. With the instrument reading ‘Fwd’ or ‘Rev’, reduce the voltage until the element resets. Record the minimum
phase-phase operate voltage.
Minimum Voltage Setting
Measured
2.1.1
2 out of 3 logic
Ensure that at least 1 Phase Overcurrent element is set to Directional. Apply balanced nominal voltage. Apply
current at a level above the 50/51 setting on phase A only at the characteristic angle for forward operation,
normally 45º lagging. Ensure no Directional Phase Overcurrent element operation occurs. Note that non-
directional Phase Overcurrent and Non-direction Earth Fault elements may operate unless disabled.
Repeat the test with Phase A current as above but also with equal current in the B phase at 180º to that in the A
phase.
1 phase current
2 phase current
No 50/51-n Operation
50/51-n operation
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......