7SR11 & 7SR12 Performance Specification
©2017 Siemens Protection Devices Limited
Chapter 3 Page 24 of 56
2.6
47 Negative Phase Sequence Voltage
2.6.1
Reference (47)
Parameter
Value
Vs
Setting
1, 1.5… 90V
V
s
Guard
Guard Setting
1, 1.5, …199.5, 200 V
Hyst.
Hysteresis
0, 0.1… 80%
t
d
Delay setting
0.00, 0.01…20.00, 20.10… 100, 101… 1000, 1010… 10000,
10100… 14400 s
2.6.2
Operate and Reset Level (47)
Attribute
Value
V
op
Operate level
100 %
Vs
,
±
2 % or
±
0.5 V
Reset level
(100%-Hyst.) x V
op
± 1% or ± 0.25V
Repeatability
±
1 %
Variation
-10 °C to +55 °C
≤
5 %
f
nom
± 5 %
≤
5 %
2.6.3
Operate and Reset Time (47)
Attribute
Value
t
basic
Element basic operate time
0V to 2.0
xVs
, 80 ms,
±
20ms
0V to 10
xVs
, 55ms,
±
20ms
t
op
Operate time following delay
t
basic
+
t
d
,
±
2 % or
±
20ms
Repeatability
±
1 % or
±
20ms
Overshoot time
< 40 ms
Disengaging time
< 90 ms
Summary of Contents for Argus 7SR11
Page 1: ...Energy Management 7SR11 7SR12 Argus Overcurrent Relay Reyrolle Protection Devices ...
Page 2: ......
Page 4: ...7SR11 7SR12 Argus Contents 2015 Siemens Protection Devices Limited Page 2 of 2 ...
Page 170: ...7SR120 Technical Manual Chapter 4 Page 2 of 84 2017 Siemens Protection Devices Limited ...
Page 174: ...7SR120 Technical Manual Chapter 4 Page 6 of 84 2017 Siemens Protection Devices Limited ...
Page 196: ...7SR120 Technical Manual Chapter 4 Page 28 of 84 2017 Siemens Protection Devices Limited ...
Page 242: ...7SR120 Technical Manual Chapter 4 Page 74 of 84 2017 Siemens Protection Devices Limited ...
Page 244: ...7SR120 Technical Manual Chapter 4 Page 76 of 84 2017 Siemens Protection Devices Limited ...
Page 246: ...7SR120 Technical Manual Chapter 4 Page 78 of 84 2017 Siemens Protection Devices Limited ...
Page 254: ...7SR11 7SR12 Installation Guide Chapter 5 Page 2 of 32 2017 Siemens Protection Devices Limited ...
Page 358: ...7SR11 7SR12 Applications Guide Page 2 of 48 2017 Siemens Protection Devices Limited ...
Page 405: ......