Extinguishing
88
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
32.2 Degraded mode link E3G110 option
Allows extinguishing to be activated automatically even if the main CPU fails.
Depends on 2 detectors.
The detectors in the extinguishing SECTION must be split over
2 independent
detector lines.
E3M071
B3Q440
E3G080
K1
CPU
E3X10.
or
B3Q...
E3G110
K1
24/5V
1......4
K1
ST1
ST8
ST10 K1
E3M071
ST10 K1
I-Bus
Manual activation
interactive
detectors
CC11, CI11
DM1103
E3G110
Z1I030/050
Note:
'ST10'
connector only provided for
E3M060
(MS9i),
E3M071
(interactive),
E3M171
(interactive Ex),
E3M080
(collective) and
E3M111
(AnalogPLUS)
'MIMIC DISPLAY'
connector for
E3M141
32.3 Key data
'Delayed' area valve
–
Activation delay of 0..240 s
–
Limitation of activation period of 0..240 s or until reset
–
Monitored line
–
Line can be adjusted to area valve
'Non-delayed' main valve
(activation of pneumatic path)
–
Limitation of activation period of 0..240 s
–
Monitored line
–
Line can be adjusted to main valve
Alarm horn
–
Can be turned off by extinguishing operating unit or control panel
–
Monitored line
–
Activation mode active continuously/can be programmed to pulse
Illuminated panel
–
Can be shut down separately or remains active until reset
–
Monitored line
–
Activation mode active continuously/can be programmed to pulse
Manual activation
–
Directly only E3G080
–
Also functions when control panel is in 'degraded mode'
–
Line monitored
Automatic activation
–
Via detector –> control panel, parameters can be set for alarm, either for:
–
Detectors in same OBJECT
–
Detectors in different OBJECTS
–
Detectors in same or different OBJECTS
–
All detector models can be used (interactive / AnalogPLUS / collective)
Stop/block button
–
Separate monitored line
'Loss of extinguishing agent' reporting contact
–
Separate monitored line
'Extinguishing blocked' reporting contact
–
Separate monitored line
'Extinguishing activated' reporting contact
–
Separate monitored line
Local operating unit
–
Using 'Extinguishing' operating unit B3Q440
–
Usage recommended, but not compulsory
–
Max. 4 operating units possible
–
Via LON data bus with monitored line
–
Length of line up to 600 m
Fire control
–
Via control panel control output
Special feature
–
Autonomously functioning I bus component
–
Integrated degraded mode function
–
Parameter settings via AlgoWorks
–
User functions saved on E3G080
–
Several extinguishing SECTIONS can be interlocked with one another
–
Automatic adjustment function