28.5 LON I/O board K3I110
Input/output board
–
16 programmable monitored control inputs
–
16 programmable control outputs
Measurements:
122 x 220 x 14 mm
K3I110
H23G230
K3I110
28.6 Display devices B3Q580 and B3Q590/595
Both devices with identical sizes
For recessed mounting, see page 55
B3Q580
H23G230
B3Q590
B3Q595
H23G230
B3Q590 (Nordic lock)
B3Q595 (KABA lock)
Function
B3Q580 plain text display terminal
B3Q590/595 plain text operating terminal
LCD 2x40 characters, yellow backlit
Alarm events display
All OBJECTS from
1..16 selectable SECTIONS
All OBJECTS per station (cannot be selected)
Fault events display
Can be selected (yes/no via AlgoWorks)
Can be selected (yes/no via AlgoWorks)
Selectable display operating modes
14 (can be selected via AlgoWorks)
14 (can be selected via AlgoWorks)
Buzzer can be turned off
3 programmable LEDs
–
'Continue' function key
(also used for Buzzer off + lamp test)
(also used for Buzzer off + lamp test)
'Acknowledge' / 'Reset' function keys
–
Key switch for operating access
–
B3Q590 = Nordic
B3Q595 = KABA
Can be fitted in housing H23G230
Insertable inscription strips
Operating voltage
9...45 V DC
9...45 V DC
Current consumption at 24 V
Standby
: 20 mA / max: 180 mA
Standby
: 18 mA / max: 185 mA