26.8 'FD20' detector line
Number of addresses per line: Max. 126, –> limitations for certain device types
1)
Only 1 T-branch possible between 2 devices
2 Loop lines
FDO221
BFST
Feedback-
contact
FDM22x
FDO/FDOOT/FDT2x1
E3M141
DLR11
..
FDCIO222
Programmable control output for 1 external response indicator in each SintesoTM detector base
FDOOT221
FDO241
FDCI222
1...........4
DJ1191/92
FDT221
FDT241
FDCL221
Stub line
max. 32 devices
FDS221
FDS221
FDT241
FDO221
FDT221
FDO221
FDS221
1..4
1..4
FDOOT241-9
FDL241-9
FDF2x1-9
T
br
anch
FDOOT241-9
Stub line
max. 32 devices
Stub line
max. 32 devices
False
ceiling
Room 104
Room 102
allocated to the detector
Room 101
Room 103
allocated to the detector
ZONE (Default)
allocated to another ZONE
Means of linking for external
response indicators
1
2
3
Basic programming
AI external is allocated to the
logic detector ZONE
-> most frequent application variant (Default)
synchronous with the detector AI internal
AI external is allocated to detector
in the base
-> e.g. for detectors in hollow floors
or false ceilings
allocated to another ZONE
AI external is treated as a control output
-> can thus be allocated to any logic
ZONE or several ZONES
2
ZONE 5
ZONE 7
ZONE 9
3
1
FDnet
max. 126 addresses / 210
Ω
1) For details, see document 001508