Alarming concept
103
Building Technologies
008725_h_en_--
Fire Safety & Security Products
06.2011
37.2 Defining alarm organization
–
The CS1140 fire detection system has up to 64 programmable organizational
levels (AREAS)
–
Different "alarming variants" are possible (can be selected per OBJECT)
–
The "V1" and "V2" time memories should be defined individually
–
The "V2" time memory can be defined per OBJECT (if needed)
–
Various country-specific special functions are available
–
The alarm organization is programmed individually (via maintenance PC)
37.3 Designing the system operating unit
The place from which the fire detection installation is operated must be defined
from an organizational standpoint
If necessary, a double operation unit must be provided
Particularly exposed operating units should be fitted with lockable plexi glass
doors (H26T... + Z3S...)
The type of event and geographic location are displayed on the operating unit in
plain text
The names of the geographic locations (rooms etc.) are defined individually us-
ing "user text" (via maintenance PC)
If necessary, an extra
event-related instruction
, known as 'measures text' can
be assigned to certain rooms
The fire detection installation may only be operated by instructed persons (ac-
cess to the operating unit is therefore protected by password or key switch)
For details of the AlgoPilot operating console, see page 47