REPLACING AlgoRex DEVICE
Simple replace-
ment process
for AlgoRex
manual call
points and DC
modules
The process of replacing AlgoRex interactive manual call points and DC modules is a simple
one. If the device is found to be defective, the corresponding element can be set using the
'Replace device -> On operating mode' to the 'Replace device' operating mode command.
The operating personnel can then replace the defective device.
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Replace device -
> On operating
mode
The command is available at element level. A message to this effective is displayed on the ter-
minal. Only one element can be replaced per replacement session. The 'Replace device -> Off
operating mode' or restarting the station ends this operating mode.
Perform the following steps to set a defective manual call point to 'Replace' operating mode:
Step
Action
Result / Comment
1
Press
button
<Faults>
2
Select defective
manual call point
Use the scroll keys on the display
3
Press
softkey
<Functions for sel. message..>
4
Press
softkey
<More functions..>
5
Press
softkey
<Device replace mode -> ON>
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'
This command
switches off the supply
to the line to which the element selected is connected.