Operating instructions
Œ•Ž
58
Building Technologies
A6V10225450_b_en_--
Fire Safety
2017.09.07
Activating / deactivating ELEMENT
What is this?
Elements can be activated manually from the AlgoRex terminal.
Which elements
can be activat-
ed?
The following elements can be activated, but with different impacts:
·
Interactive detector element
·
AnalogPLUS detector element
·
FD20 detector element
·
Digital element
·
Control element
How does this
impact on the
elements?
The activation/deactivation commands have the following impacts:
Element type
Impact
Interactive detector element
·
The response indicator is activated/deactivated
·
No impact on logical status of element.
AnalogPLUS detector element
FD20 detector element
Digital element
Activation sets danger level 3, deactivation resets to danger
level 0.
Control elements
Element is activated/deactivated
Operating ac-
cess
If you still don't have operating access when starting operation work, the release procedure is
automatically called up.
Activation of an
interactive
AnalogPLUS or
FD20 element
Perform the following steps to activate one of these elements:
Step
Action
Result / Comment
1
Navigate
to the ELEMENT you
want
(Interactive, AnalogPLUS or FD20 ele-
ment)
The element selected is displayed in-
versely
2
Press
softkey
<More functions..>
3
Press
softkey
<ACTIVATE element>
Implementation messages
'
Implementing ...
'
- and -
'
Implemented
'
The element's response indicator is -
activated.