Testing MANUAL CALL POINTS
Switching over
to test mode
The system must be switched to test mode before testing can begin.
F
Also refer to following chapter:
·
"TEST CONDITION per SECTION" on page 42
·
"TEST CONDITION per LINE" on page 44
·
"TEST CONDITION per ZONE" on page 46
Testing DM11x1
/ FDM221 type
manual call
points
This procedure describes the test principle for manual call points of AlgoRex type DM1101,
DM1131, DM1151 (type KAC) and Sinteso
TM
type FDM221.
Perform the following steps to test these types of manual call point:
Step
Action
Result / Comment
1
Set corresponding manual call
point zones to 'Test condition' op-
erating mode
Test key
2
Insert test key in opening:
à
'Test
alarm' is simulated
3
Wait until response indicator on
manual call point flashes
4
Remove test key
The function test is complete.
Continue with the next manual call
point
NOTE:
Once testing is complete, the 'Test condition' operating mode must be ended.
F
Also refer to following chapter:
·
"TEST CONDITION per SECTION" on page 42
·
"TEST CONDITION per LINE" on page 44
·