Testing AUTOMATIC DETECTORS
Switching over
to test mode
The system must be switched to test mode before testing can begin.
F
Also refer to following chapter:
·
"TEST CONDITION per SECTION" on page 42
·
"TEST CONDITION per LINE" on page 44
·
"TEST CONDITION per ZONE" on page 46
Testing auto-
matic detectors
This procedure describes the test principle for automatic detectors.
Perform the following steps to test automatic detectors:
Step
Action
Result / Comment
1
Set corresponding detector to
'Test condition' operating mode.
AlgoRex
Sinteso
TM
DOT
DO
DT
FDO, FDOOT
FDT
FDM, FDS
FDC, FDL
2
Attach detector tester to detector.
Note marking!
·
The detector exchanger and
detector tester DZ1193 is
needed for AlgoRex smoke de-
tectors and neural smoke de-
tectors.
·
The detector tester RE6T is
needed for AlgoRex heat de-
tectors:
The rise in temperature is simu-
lated using a hot air fan.
·
The detector exchanger and
tester FDUD292 is needed for
Sinteso
TM
devices
Detector exchanger and tester Detector test-
er
Detector exchanger and tester
DZ1193
RE6T
FDUD292
3
Wait until the response indicator
on the detector flashes.
4
Remove detector tester.
The function test is complete.
Continue with the next detector.
NOTE:
Once testing is complete, the 'Test condition' operating mode must be ended.
+
Also refer to following chapter:
·
"TEST CONDITION per SECTION" on page 42
·
"TEST CONDITION per LINE" on page 44
·