Siemens AD-3I Installation/Wiring Instructions Download Page 1

INTRODUCTION

Model AD-3I and AD-3ILP Detectors from Siemens Industry, Inc. are System 3,
System  PXL, System SXL-EX, System SXL, System XL3, System
CP-2ER, MXL Control Panel and MXL-IQ Control Panel compatible air
duct detectors. They are designed for use in heating, ventilating, and air
conditioning duct systems. Model AD-3I uses ionization smoke detectors,
and Model AD-3ILP uses photoelectric smoke detectors to detect the pres-
ence of combustion products in a duct system. (Refer to TECHNICAL
DATA
 below for information on compatible detectors.)

When smoke or combustion products are detected, shutdown of the duct
system and/or operation of supplementary equipment is provided by the
related system control panel.

TECHNICAL DATA
Smoke Detector Compatibility

TABLE 1

AD-3I COMPATIBILITY

System/Module

Compatible Detectors

CP-2ER

DI-B3, DI-B3H

MXL/MXL-IQ Control Panel

ILI-1B, ILI-1BH

MXL/MXL-IQ Control Panel

DI-B3, DI-B3H (no accessories with

      (CZM-1/1B6 or CZM-4)

     CZM-1/1B6)

System 3

DI-B3, DI-B3H

System PXL

DI-B3, DI-B3H

System PXL (PZE-4B)

DI-B3, DI-B3H

System SXL

DI-B3, DI-B3H (no accessories)

System SXL (SZE-4R)

DI-B3, DI-B3H (no accessories)

System SXL (SZE-8A)

DI-B3, DI-B3H (no accessories)

System SXL-EX

DI-B3, DI-B3H

System SXL-EX (SZE-4X)

DI-B3, DI-B3H

System SXL-EX (SZE-8AX)

DI-B3, DI-B3H

System XL3 (INX-3)

ILI-1B, ILI-1BH

System XL3 (ZNX-3)

DI-B3, DI-B3H

INSTALLATION/WIRING INSTRUCTIONS

Models AD-3I and AD-3ILP
AIR DUCT DETECTORS

P/N 315-093234-7

Siemens Industry, Inc.
Building Technologies  Division
Florham Park, NJ

Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Summary of Contents for AD-3I

Page 1: ...el TECHNICAL DATA Smoke Detector Compatibility TABLE 1 AD 3I COMPATIBILITY System Module Compatible Detectors CP 2ER DI B3 DI B3H MXL MXL IQ Control Panel ILI 1B ILI 1BH MXL MXL IQ Control Panel DI B3 DI B3H no accessories with CZM 1 1B6 or CZM 4 CZM 1 1B6 System 3 DI B3 DI B3H System PXL DI B3 DI B3H System PXL PZE 4B DI B3 DI B3H System SXL DI B3 DI B3H no accessories System SXL SZE 4R DI B3 DI ...

Page 2: ...Q I L X M L X M 6 B 1 1 M Z C y r o t c a F t e S y d a e t s D E L d e R v p u s n i F F O 5 1 I 3 D A s e i r o s s e c c a o N 3 X N I 3 L X m e t s y S d e t c e l e S l o r t n o C t a l e n a P y r e v e s e h s a l f D E L d e R s d n o c e s 3 v p u s n i F F O 0 3 I 3 D A 0 3 P L I 3 D A Q I L X M L X M l e n a P l o r t n o C d e t c e l e S l o r t n o C t a l e n a P y r e v e s e h s ...

Page 3: ...On MXL Systems the alarm is indicated on the Control Panel display and on the optional printer See system manuals for further infor mation After a fire is extinguished and all products of combustion are cleared from the duct system each system can be reset at its respective control panel or remote annunciator if available Trouble Condition A trouble condition from an AD 3I 3ILP is indicated by vis...

Page 4: ... the turbulence See Figure 1 A 12 inch by 12 inch access hole should be cut in the duct adjacent to the detector to permit checking and cleaning of the sampling tubes if necessary 4 Figure 1 Typical Mounting of Duct OUTLET SAMPLING TUBE INLET SAMPLING TUBE AT LEAST SIX DUCT WIDTHS Locate the air duct detector in the air handling system as shown in Figure 2 and in conformance with NFPA Pamphlet No ...

Page 5: ...ix the adhesive backed template 5 to the side of the ductwork c Drill the four 0 110 diameter holes with a No 35 drill bit and cut or punch out two 7 8 inch diameter holes as indicated on the template d Attach the appropriate model housing to the air duct using two No 10 11 2 inch screws 6 and also using two No 10 1 inch screws 7 with lockwashers 8 e Cut a 12 inch by 12 inch access hole in the duc...

Page 6: ...ubber Stopper 10 Bracket 11 Screw 3 16 12 Screw 8 32 13 Plug 14 Detector DI B3 DI B3H ILI 1B or ILI 1BH 15 Detector ILP 1 or ILP 2 16 Cover Gasket 17 Ionization Detector Cover 18 Photoelectric Detector Cover P N 305 093076 19 Screw No 6 20 Sensitivity Test Jack Lid Figure 3 Exploded View 6 CAUTION DISCONNECT POWER PRIOR TO SERVICING AIR DUCT DETECTOR DETECTOR ...

Page 7: ...nlet sampling tube at the job site as described below TABLE 5 SAMPLING TUBE SELECTION CHART Sampling Tube Standard Outside Duct Width Model No Tube Length 1 ft 93 4 in or less STA 2 2 ft 1 ft 93 4 in 3 ft 33 4 in STA 3 3 ft 6 in 3 ft 33 4 in 6 ft 33 4 in or less STA 6 6 ft 6 in 6 ft 33 4 in 9 ft 93 4 in or less STA 10 10 ft Greater than 9 ft 93 4 in Consult factory Note Each model is manufactured ...

Page 8: ...nd outlet air sampling tubes with 3 16 screws 11 NOTE When attaching brackets be sure to align tubes properly See Figure 4 c Install the inlet tube 3 by inserting it through the air sampling chamber as shown in Figure 3 Face sampling tube holes into the air stream Figure 4 and secure to the housing with 8 32 screws 12 d Install the outlet tube 4 by inserting it into the upper socket of the air sam...

Page 9: ...ion See Tables 1 and 2 Do not use any other detector See Figure 3 items 14 and 15 Programming ILI 1B ILI 1BH ILP 1 ILP 2 Detectors Model AD 3I 3ILP ducts using ILI 1B ILI 1BH ILP 1 or ILP 2 detectors can be programmed to respond at a specific and unique system address Program each detector using the Model FPI 32 Programmer Tester See the FPI 32 Manual P N 315 090077 The ILP 2 requires FPI 32 Rev 1...

Page 10: ...ER System PXL System SXL EX System SXL MXL MXL IQ Control Panel CZM 1 CZM 1B6 CZM 4 NOTE EOL device must be compatible with system initiating circuit Observe proper polarity where applicable 10 CAUTION 1 See Table 3 for maximum number of air duct detectors per circuit 2 If remote lamps are used the relay board option cannot be used 3 Remote lamps may not be used with the MXL MXL IQ Control Panel C...

Page 11: ... 1BH Model AD 3I or AD 3ILP TERMINAL BLOCK RED RED WIRE NUT REQUIRED BLACK BLACK ZONE WIRES FROM SIEMENS INDUSTRY INC SYSTEM XL3 CONTROL PANEL SEE TABLES 1 AND 2 OPTIONAL REMOTE ALARM INDICATOR MODEL RLI 1 OR RLI 2 OPTIONAL REMOTE ALARM INDICATOR MODEL RLI 1 OR RLI 2 TO NEXT ADDRESSABLE DEVICE NOT USED NOT USED 11 ...

Page 12: ... 2 ILI 1B or ILI 1BH Model AD 3I or AD 3ILP TERMINAL BLOCK RED RED WIRE NUT REQUIRED BLACK BLACK ZONE WIRES FROM SIEMENS INDUSTRY INC MXL MXL IQ CONTROL PANEL SEE TABLES 1 AND 2 OPTIONAL REMOTE ALARM INDICATOR MODEL RLI 1 OR RLI 2 OPTIONAL REMOTE ALARM INDICATOR MODEL RLI 1 OR RLI 2 TO NEXT ADDRESSABLE DEVICE NOT USED NOT USED ...

Page 13: ...n Installation and Maintenance Manual P N 315 083206 3 The sensitivity of addressable MXL MXL IQ Control Panel smoke de tectors can be measured at the system control panel Refer to the MXL Operation Installation and Maintenance Manual P N 315 092036 or the MXL IQ Operation Installation and Maintenance Manual P N 315 093624 as applicable 4 To ensure that the sensitivities are within factory specifi...

Page 14: ...performance This can be done by removing the sealing plug from the inlet sampling tube on the opposite side of the duct and blowing smoke directly into the inlet tube Check that the fire alarm system is activated CAUTION If the fire alarm system is connected to a central station or fire department or has external devices such as fans extin guishers etc connected notify appropriate personnel and di...

Page 15: ...N 315 095355 4 CZM 4 MXL MXL IQ System P N 315 090726 8 PXL P N 315 094131 4 PZC 4D PXL P N 315 094164 2 PZE 4B PXL P N 315 094065 4 SXL P N 315 092419 10 SXL EX P N 315 095997 5 SZE 4R SXL P N 315 092430 4 SZE 4X SXL EX P N 315 096018 4 SZE 8A SXL P N 315 092969 4 SZE 8AX SXL EX P N 315 096022 4 ZNX 3 XL3 System P N 315 088562B ZU 35 System 3 P N 315 083222 14 The detector model number is the com...

Page 16: ...P N 315 093234 7 Siemens Industry Inc BuildingTechnologies Division Florham Park NJ Siemens BuildingTechnologies Ltd Fire Safety Security Products 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Reviews: