INSTALLATION AND CONFIGURATION
2-18
Document No.: COM-00-05-16 June 2006, Revised June 2014
Version: C.1
3.
Prior to exiting the First Configuration Menu, select “Save changes then restart” to save
changes and restart the WAG.
2.6.7
UDP Port Assignments
If two or more WAGs need to communicate with each other across the Ethernet, the Slot #1 UDP
port number configured in all WAGs must be the same. However, the user may choose to isolate
WAGs from conflicting with each other by configuring the Slot #1 UDP port numbers differently.
UDP port numbers 9999 and 10000 are protected. The user cannot specify these port numbers.
To Assign UDP Port Numbers:
1.
On the First Configuration Menu, select “UDP ports” assignments to be changed. The UDP port
assignment screen appears. The UDP port assignment defaults are; 5000, 5001, 5002, and 5003.
Figure 2-19. UDP Port Assignment Screen
UDP Port Assignment Screen
2.
To keep the current UDP port assignment, press
ENTER
. If not, enter the assignment value for
slots 1 through 4 and then press
ENTER
.
When finished, the user will be returned to the First Configuration Menu. The UDP
assignments are listed.
3.
Prior to exiting the First Configuration Menu, select “Save changes then restart” to save
changes and restart the WAG.