Analog outputs are available on the optional I/O modules you can connect to the
base of your meter.
Calculate your zero scale and full scale values based on the measured value and
the analog output range of your meter.
Make sure that the analog output port that you want to use is properly connected
to an analog receiver.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Expansion Modules > Option I/O Modules
and select the
module tab that corresponds to the option module with the analog output you
want to configure.
4. Select the analog output channel and click
Edit
. Enter the meter password if
prompted. The setup screen for that analog output is displayed.
5. Configure the analog output by selecting the parameter and clicking
Edit
.
Parameter
Value/Range
Description
Zero scale
0 to ±10
9
The minimum source value that matches the minimum
analog output signal.
Full scale
0 to ±10
9
The maximum source value that matches the
maximum analog output signal.
Port
–
The physical analog output port connection.
Mode
Voltage, current
Determines whether the analog output is monitoring
voltage or current.
Related Topics
Option I/O modules configuration
Digital inputs
Digital input applications
Digital inputs are typically used for monitoring the status of switches or contacts,
such as status contacts on circuit breakers.
They can also be used for pulse counting or input metering applications, such as
WAGES (water, air, gas, electricity, steam) monitoring, or conditional energy
applications, or IRIG-B time synchronization.
Typical applications for the digital input are switch or relay status monitoring, KYZ
transitions, AC detection.
Pulse mode
If you set Input Mode to PULSE, a pulse is generated at the Trigger output when
the State output changes from OFF-to-ON. No pulse is generated when State
changes from ON-to-OFF.
76
7EN05-0390-00
Summary of Contents for 9810 Series
Page 1: ...9810 series User manual 7EN05 0390 00 09 2018 www usa siemens com pds ...
Page 4: ......
Page 12: ......