See the ION Reference, available from www.usa.siemens.com/pds, for detailed
information on the SNMP Mapping, SNMP Options and Alarm Options modules.
Default SNMP mapping
Enabling SNMP provides SNMP access to the meter values linked to the SNMP
Mapping module.
You can configure the SNMP Mapping module to link to different meter values. By
default, the following meter values are linked to the SNMP Mapping module:
I a
kVAR tot
Vll ca
Vln avg
Ib mean
kW sd mx del-rec
I b
kVA tot
Vll avg
Freq
Ic mx
kW sd del
I c
PF sign tot
Vln a
Ia mx
Ic mean
kW sd rec
I avg
Vll ab
Vln b
Ia mean
kW sd mx del
kW sd del-rec
kW tot
Vll bc
Vln c
Ib mx
kW sd mx rec
kVAR sd mx del
kVAR sd mx rec
kVAR sd mx del-rec
kVAR sd del
kVAR sd rec
kVAR sd del-rec
kVA sd mx del
kVA sd mx rec
kVA sd mx del-rec
kVA sd del
kVA sd rec
kVA sd del-rec
kWh del
kWh rec
kWh del-rec
kVARh del
kVARh rec
kVARh del-rec
kVAh del
kVAh rec
kVAh del-rec
The following meter information is always provided by default and cannot be
configured:
Voltsmode
Model number
Serial number
Device name
Firmware version
MIB version
If you change your meter’s default values you must modify the custom MIB file to
reflect the new values.
Changing your meter’s default SNMP configuration assumes that you have an
advanced understanding of ION architecture, SNMP, and the communications
network and power system that your meter is connected to.
See the ION Reference, available from www.usa.siemens.com/pds, for detailed
information on the SNMP Mapping module.
Configuring your SNMP MIB file
You must configure your MIB file if you have modified the default SNMP
information provided by the meter in order for the MIB file labels to reflect the
modified values.
Download the ION MIB file from www.usa.siemens.com/pds.
NOTE:
You should only configure the variable name and description.
Changing other fields in your MIB file may cause the client software to report
problems or return errors when trying to retrieve or view parameters.
The variable name must conform to the following rules:
•
The first character must be a letter.
•
The first character must be lower case.
•
The name must not contain any special characters such as *, ?, &.
•
The name must not contain spaces.
1. Open your meter’s MIB file in a text editing program (such as Notepad).
2. Update the variable name and description so they match the meter values
connected to the SNMP Mapping module.
7EN05-0390-00
65