5. Press
Select
to enter the
Test Mode Screens
. Enter the meter password if
prompted and press
Select
.
The
Test Mode
menu displays briefly before switching to the first
Test Mode
screen.
6. View the test mode screens by pressing
Up
or
Down
.
7. Press the Home button to return to
Test Mode Screens
. Press
Down
to
highlight
Exit Test Mode
, then press
Select
.
Putting your meter in test mode using ION Setup
You can put your meter into test mode using the ION Setup.
NOTE:
You cannot place a revenue-locked meter into test mode.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Verification
and select the
Verification
tab.
4. Select
Test Mode
and click
Display
.
Your meter is now in test mode, and the
Test Mode
screen is displayed.
5. Select the different tabs to view your meter’s test mode values and modify
test mode parameters.
6. Click
Close
to take your meter out of test mode.
Device-specific information
Manufacturing-related information about the meter is available from the Factory
module or through Modbus commands.
The meter’s Factory module stores meter details such as device type, serial
number and vendor name. You can use ION Setup in advanced mode to view the
contents of the Factory module’s setup registers. Similarly, you can use Modbus
commands to read the Modbus registers mapped to the corresponding Factory
module’s registers.
NOTE:
Not all ION device setup registers are mapped to Modbus registers by
default.
Other device-specific details, such as Product Code, are not stored in the Factory
module. Product Code (also known as Modbus Product ID) is a number that the
manufacturer assigned to a product to uniquely identify it, for use by systems that
specifically require this information. You can use the device’s Modbus map and
Modbus commands to read the Modbus Product ID.
The
ION Reference
describes the Factory module in detail. You can download the
ION Reference
and your device’s Modbus map from www.usa.siemens.com/pds.
Troubleshooting
Option module troubleshooting
Your meter’s option modules operate sequentially; if one module is non-functional
all downstream modules may be affected.
If your meter cannot communicate with an option module, by default it cycles
power to that module and all downstream modules, making multiple attempts to
communicate. After the maximum number of communication attempts has been
exceeded the meter will remove power to that module and all downstream
modules.
200
7EN05-0390-00