6. Select the parameter to configure.
NOTE:
Configuring any parameter resets the incremental energy values
recorded by your meter.
Parameter
Range
Description
Start time
12:00 am to
11:59 pm
The incremental energy first interval’s start time. The
start time must be prior to the end time for energy
accumulation.
End time
12:01 am to
12:00 am
The end time for incremental energy.
The end time must be after the start time and be less
than or equal to 12AM (midnight).
Interval duration
Configurable
The increment period for the incremental energy
duration.
7. Click
OK
to save your changes.
Conditional energy
Conditional energy allows you to define an accumulation period for real and
reactive energy using one of your meter’s digital inputs.
You can use conditional energy to track four-quadrant accumulated energy during
a specific period. For example, you can track accumulated energy values during a
particular process that is controlled by a programmable logic controller (PLC).
Conditional energy is accumulated until it is reset. The conditional energy reset
date and time information is stored in the meter’s event log.
Related Topics
Configuring conditional energy using ION Setup
You can enable and configure conditional energy settings using ION Setup.
When configuring your meter, the configuration interface may show all of the
possible ports, regardless of what is physically available on your meter.
One of your device’s digital inputs must be connected and configured to define
when conditional energy is accumulated.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Energy Applications > Digital Input Based
. Review the digital
inputs assigned to applications to help ensure there are no conflicting usages.
4. Select
Conditional Energy
and click
Edit
. The
Conditional Energy Setup
screen is displayed.
5. Select
Enabled
to enable the conditional energy feature.
6. Click
Select
to define the digital input. The input’s state determines whether
conditional energy is accumulated. When this digital input is on, conditional
energy is accumulated.
NOTE:
It is recommended to set
Assigned Input
to No Connection to
disable the conditional energy feature by removing any port associations.
7. Click
OK
to save your configuration.
186
7EN05-0390-00