4. Select
Voltage
and click
Learn
.
NOTE:
Learning is not supported for
Current Swell
and
Current Sag
.
NOTE:
You can manually configure the limit values by selecting the
parameter and clicking
Edit
.
The
Global Setpoint Learning
screen is displayed.
5. Click
Setup
.
The
Alarm Learning Setup
screen is displayed.
Sag/swell limit learning parameters
Parameter
Value/Range
Description
Install mode
Automatic,
Manual
•
Automatic: the learned values are automatically
applied.
•
Manual: the learned values are stored for you to
review and enter.
Duration
1-365
Days for maximum learning duration.
6. Configure the sag/swell limit learning parameters and click
Save
.
7. Click
Start
to begin sag/swell limit learning.
•
Learning status and time remaining are indicated in the Learning Status
box.
•
Click
Abort
to stop sag/swell limit learning.
8. Apply the learned sag/swell limits.
–
Automatic: the limits are automatically applied unless there are issues with
the learning process.
–
Manual: navigate to
Alarming > Sag/Swell
. Select
Voltage
and click
Learn
. Click
Install
to apply the learned limits.
NOTE:
If you click
Install
while learning is in progress (in either manual or
automatic installation mode), it stops the learning process and prompts
you for confirmation that you want to stop learning and install the learned
limits. Once you have confirmed, the learned limits are automatically
installed or prepared for manual installation.
Implementing transient learning using ION Setup
You can use ION Setup to implement voltage transient learning, which analyzes
your power system and recommends settings.
NOTE:
Your meter’s power system must be stable in order to learn valid
transient thresholds.
1. Start ION Setup.
2. Open the Setup Assistant for your meter.
3. Navigate to
Alarming > Transient
.
4. Select
Transient/Waveshape
and click
Learn
.
The
Global Setpoint Learning
screen is displayed.
5. Click
Setup
.
The
Alarm Learning Setup
screen is displayed.
6. Configure the transient threshold learning parameters and click
Save
.
136
7EN05-0390-00